Descargar Imprimir esta página

Siemens 6ES7136-6BA00-0CA0 Informacion De Producto página 25

Módulos failsafe

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 43
WARNING
To achieve SIL3/Cat.4/PLe with this wiring, you must use suitably qualified sensors.
WARNING
All cables need to be laid in such a way that they are resistant to interference voltage. Use shielded cables.
Assignable parameters for Application 6
Table 4
Parameters for Application 6 of F-AI 4xI 0(4)..20mA 2-/4-wire HF
Parameter
Standard value
Discrepancy time
Tolerance window %, absolute
Tolerance window %, relative
Behavior after channel faults
Interference frequency suppression
Evaluation of the sensors
Measuring range
Diagnostics: Wire break
Smoothing
Use of radio devices and cell phones
WARNING
Unexpected malfunctions of machines caused by radio devices/cell phones
Malfunctions are possible when radio devices or cell phones are used in the direct proximity of F-I/O. This can result in
death, serious injury or property damage.
If you scan the 2D matrix code/ID Link or use the "SIEMENS Industry Support App" with a powered-on F-I/O, then deactivate
all radio connections of the radio device/cell phone beforehand. Alternatively, power off the F-I/O before scanning.
Power off radio devices in the immediate proximity of the F-I/O.
Product Information for the Documentation of ET 200SP Fail-safe Modules
A5E32586870-AK, 02/2024
Value range in safety mode
MIN
MAX
100 to 30000 ms
2.0 to 20.0%
2.0 to 20.0%
Passivation of the entire F-module
Passivation of the channel
50 Hz
60 Hz
1oo2 evaluation (max. SIL3/Cat.4/PLe)
0 to 20 mA
4 to 20 mA
(in the measuring range 4 to 20 mA)
Disable
Enable
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles
25

Publicidad

loading