Descargar Imprimir esta página

Biral ModulA RED Serie Instrucciones De Instalación Y Funcionamiento página 11

Ocultar thumbs Ver también para ModulA RED Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

11
english
For the delivery of a liquid with density that
Note
differs from water and/or kinematic viscosity,
the delivery output is reduced.
– Domestic hot water:
Permissible water hardness: max. 35 °fH (20 °dH)
To counter the risk of lime deposits, for domestic
hot water systems we recommend:
Warning
The pump may not be used to deliver
combustible media such as diesel and fuel.
Warning
The pump may not be used to deliver
aggressive liquids such as acids or seawater.
3.3 Operating conditions
– Medium temperature:
ModulA RED
+15 °C to +110 °C
ModulA GREEN –10 °C to +110 °C
ModulA BLUE
+15 °C to +85 °C
(recommended for domestic
hot water systems: max 65 °C)
– Operating pressure:
The maximum permissible operating pressure is indicated
on the nameplate. (6 bar, 10 bar or 16 bar)
Minimum operating pressure at the pump intake ports
(intake pressure ) at 500 m above sea level:
At 75 °C water temperature
At 95 °C water temperature
At 110 °C water temperature
Per ±100 m height
– Ambient temperature:
0 °C to 40 °C
(water temperature below 65 °C)
max. 25 °fH (14 °dH)
(water temperature below 85 °C)
Hardness level max. 25 °fH (14 °dH)
Medium temperature < 65°C
Single pump
Dual pump
ModulA...
ModulA-D ...
0,10 bar
0,90 bar
0,35 bar
1,20 bar
0,65 bar
1,50 bar
±0,01 bar
±0,01 bar