12
EN
Inserting the dehumidifier
Remove the transport screws marked with A, B and C
located on the top and the right of the unit.
Note that the unit may only be inserted into the metal
case when the mortar is completely dry and the metal
case is permanently fixed in place.
Before the dehumidifier can be inserted into the metal
case, the transverse bracing must be removed. Once
the unit has been correctly inserted into the metal
case, it is fixed to the metal case using the screws
provided.
03.03
Water-side connections
Cooling circuit
Supply/Return
Condensation
Water circuit
Provision of a water filter at the inlet of the
dehumidifier is recommended in order to protect the
water circuits of the unit.
Pipe dimension
Connection
d
≥ 16 mm
3/8" M
in
d
≥ 16 mm
3/4" M
in
Use REHAU pipe RAUTHERM-S or RAUTITAN for the
hydraulic connections to the dehumidifier (feed and
return) and observe the applicable local regulations.
For the correct connection to the manifold of the
embedded radiant cooling system and the setting of
the correct flow rate, please observe the relevant
installation instructions and the applicable local regu-
lations. The nominal flow rate of the water circuit of
this dehumidifier is 220 l/h.
Use suitable connection technology and suitable
sealing material so that no water can escape in an
uncontrolled fashion at the unit connection.
Carefully vent the water circuit using the relevant valve
on the unit. The valve is located under the marked
cover, which can be dismantled with two screws.
To avoid the formation of condensation on metallic
connections, these must be insulated.
1
2
3
Cover with vent valve behind it
1
Water Return 3/8" M
2
Water Supply 3/8" M
3
Condensation drain
To prevent the formation of bad odours from the waste
water, it is important to connect the condensation
drain to a siphon. To facilitate cleaning, mount the
siphon in an easily accessible place.