08
EN
02.03
Technical data
Power supply
Electrical power
1), 3)
Maximum current consumption
Switch-on current (LRA)
Air flow rate (clean filter)
Refrigerant R134a
Operating range – temperature
Operating range – relative humidity
Dehumidification capacity
Cooling capacity in dehumidification with cooling mode
Water-side capacity in dehumidification mode
Water-side capacity in dehumidification with cooling mode
Water flow rate
Pressure loss in the water circuit at 220 l/h
Dimensions (L x H x B)
Weight with filled water circuit
1)
Air: 25 °C, 65 % relative humidity / water: 16 °C, 220 l/h
2)
Dehumidification capacity and cooling capacity measured according to DIN EN 810 and DIN EN 1397
3)
In dehumidification mode and dehumidification with cooling mode
34
3
4
1
1), 2), 3)
1), 2)
1)
358
2
A
6
5
340
690
727
230 V AC, 50 Hz
450 W
3,5 A
20,0 A
180 m³/h
400 g
10 – 32 °C
45 – 98 %
22 l/d
1150 W
1180 W
1)
1600 W
220 l/h
24 kPa
727 mm x 695 mm x 200 mm
37,3 kg
200
B
C
Cover with vent valve behind it
1
Condensation drain 3/4" M
2
Water Return 3/8" M
3
Water Supply 3/8" M
4
Cable bushing
5
Electronics box with display
6
,
,
Transport screws, remove
A
B
C
before installation