6 OPERATIVE INSTRUCTIONS
6.1 USING THE INSTRUMENT IN A SINGLE PHASE SYSTEM
The Instrument can be used on installation with overvoltage CAT III 600V~
between the inputs and to ground. Do not attempt to take any voltage
measurement exceeding the limits indicated in this manual. Exceeding the
limits could cause electrical shock or damage to the instrument.
Fig. 2: Instrument's connection in single phase system
De-energize the plant under test before connecting the instrument. Take all
the safety precautions before taking actions on the plant.
1. De-energize the plant under test before connecting the instrument.
2. Insert alligator clips in the safety banana test leads.
3. Connecting alligator clips in the plant as indicated in Fig. 2.
4. Re-energize the plant under test.
5. How to start a Recording:
• If no recording was performed or if the recording data had been already downloaded
to a PC, press the START/STOP key for 3 seconds. The STATUS LED will be
blinking for the same time, then light will become stable for 1 second and the
instrument will start the recording
• If the recording data had not been already downloaded to a PC and the operator
wants to overwrite these data, press the START/STOP key for 6 seconds. The
STATUS LED will be quickly blinking during the key pressing for the same time, then
the LED will become stable for 1 second and the instrument will start the recording.
The old recording will be deleted and overwritten by the new one. The
instrument will wait for the next minute beginning (second=00) and the STATUS LED
will get a double blinking. After that the recording starts and the STATUS LED will
blink every 3 seconds. The instrument is storing the data.
CAUTION
CAUTION
EN - 7