6. Specifications Phasak
MODELO
CAPACITY *
INPUT
Low transfer voltage
Voltage return - high
Range Volt
Transfer voltage - high
Voltage return - high
Frequency range
Phase
Power factor
OUTPUT
Output voltage
Volt AC regulation (Battery mode)
Frequency range (synchronized range)
Frequency range (Battery mode)
AC Mode
Overload
Battery Mode
Peak current value
Harmonic distortion
Red <> Battery
Inverter <> By-pass
Transfer time
Inverter <> ECO
Type of wave
EFFICIENCY
AC Mode
ECO Mode
battery Mode
BATTERY
Type and number
Model
Recharge time
Standard
Charging current
Charge Volts
PHYSICAL CHARACTERISTICS
Metering, Pr X An X Al
Tower Box
Net weight (kg)
ENVIRONMENTAL CONDITIONS
Relative humidity (without condensing)
Noise level
Operating altitude **
Operating temperature
NEGOTIATION
Smart RS-232 o USB
SNMP Optional
All manuals and user guides at all-guidesbox.com
ON-LINE 3P/3P
PH 9283 (3P / 3P)
30000 VA / 30000 W
110 VAC(Ph-N) ± 3 % at 50% Load
176 VAC(Ph-N) ± 3 % at 100% Load
Line with low voltage +10V
300 VAC(L-N) ± 3 % at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
Line with high voltage -10V
46~54Hz 56~64Hz
Three phases with earth
≧ 1 .0 @ 100% of the load
3 x 400 VAC (3Ph+N)
360/380/400/415VAC (Ph-Ph)
208*/220/230/240 VAC (Ph-N)
46Hz ~ 54 Hz @ 50Hz system
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
Pure Sinusoidal
95.5%
94,5%
12V / 7AH x 64 (16+/16 adjustable)*4
9 hours to recover 90% of capacity
1.0~12.0A ±10% (Adjustable)
+/- 13.65 VDC * N ± 1% (N = 16~20)
815 x 300 x 1000 (mm)
230
<95 % RH @ 0- 40°C
< 65 dBA @ 1 meter
0 ~ 40°C (Battery life is reduced with temp. > 25°C)
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7,8,10,, Linux, Unix, y MAC
Power Management with SNMP manager and web browser
PH 9283 - PH 9284 .
PH 9284 (3P / 3P)
40000 VA / 40000 W
± 1%
3:1 (max.)
0 ms
<10 ms
95.5%
96%
94,5%
12V / 9 AH x 64 (16+/16 adjustable)*x 4 línes
1.0~12.0A ±10% (Adjustable)
260
< 70 dBA @ 1 meter
< 1000m
99 / 100