Quick start guide
English
Airflow cones are essential instruments for direct measurement of airflow ventilation and
air-conditioning systems. Si-K25, Si-K85 cones can be used with the Kimo Ø 100 mm vane
anemometers; K35, K75, K120, K150 cones with the Kimo Ø 8 mm hotwire anemometers from
Class 110, 210 and 310 portable instruments.
Si-K25, Si-K85 air flow cones with Ø 100 mm vane anemometers
Airflow
Integrated
cone
straightener
HVAC
system
1
Put the Ø 100 mm vane probe on the cone
• Open lever and put the vane probe on the end of the cone.
• Put the vane probe at the bottom of the slot and close the lever.
For a measure in exhaust, put the vane with the arrow turned towards the inside of the cone.
For a measure in supply, put the vane with the arrow turned towards the outside of the cone.
Measure in exhaust
2
Put the cone on the air vent
3
Airflow measurement
Refer to the user manual of the handheld anemometer used, in particular the section on display and flow measurement.
4
Storage
During storage, the lever dedicated to holding the vane probe should be closed to reduce the risk of
damage during storage or transport. Storage temperature: -20 to 60 °C.
Measurement principle
The Kimo Si-K25 and Si-K85 cones have a built-in hon-
airflow
eycomb airflow straightener that reduces turbulence and
enables more accurate airflow measurements. They are
designed for accurate measurements of both straight and
turbulent airflow on all major ventilation grilles and plate
outlets, including multidirectional ones.
These cones feature a compact unibody design with no
parts to assemble, making them easy to handle, especially
in tight spaces.
Measure in supply
Lever opened
Hold the cone by the cone handle. Do not hold
the assembly by the vane probe handle.
Position the cone against the wall (the support).
Centre the cone for best results.
Make sure the cone is tight against the wall.
Do not pull on the probe handle when removing
the Ø 100 mm vane probe from the cone.
K35, K75, K120, K150 air flow cones with Ø 8 mm hotwire anemometers
Measurement principle
The direction and the homogeneity of the incoming and outcoming air flow are often disrupted by the
geometry of the HVAC grilles. Therefore, it is necessary to funnel the flow to the probe's sensor.
The probe and its sensing element are located in a well known section of the cone which guarantees a
correct measurement.
1
Put the Ø 8 mm hotwire probe on the cone
Slide the hotwire anemometer probe red protection
towards the bottom of the probe.
Clip the probe into the slide on top of the cone's handle.
Remember to slide the protection back on the sensing
element.
HVAC
system
Lever closed
Probe for velocity
measurement
3
Airflow measurement
Refer to the user manual of the handheld anemometer used, in particular the section on display and flow measurement.
Red point at the bottom of the hot wire probe
must face airflow.
EXHAUST
HVAC
Sensing
system
element
Cone
Air flow
direction
Red point
Probe for velocity
measurement
2
Put the cone on the air vent
Position the cone against the wall (the support).
Centre the cone for best results.
Make sure the cone is tight against the wall.
SUPPLY
Sensing
element
Cone
Air flow
direction
Red point