TECHNICAL DATA
MODEL
TYPE
OUTPUT
(1)
DELIVERY
(1)
FUEL
- Net calorific value
- Density
- Viscosity at 20 °C
OPERATION
PUMP
delivery (at 20 bar)
pressure range
fuel temperature
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
IN CONFORMITY WITH EEC DIRECTIVES
NOISE LEVELS
(2)
APPROVAL
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
ELECTRICAL DATA
MOTOR IE1
MODEL
ELECTRICAL SUPPLY
ELECTRIC MOTOR
IGNITION TRASFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
MOTOR IE2
MODEL
ELECTRICAL SUPPLY
ELECTRIC MOTOR
IGNITION TRASFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
VARIANTS
Model
Code
3470400 - 3470410
RL 64MZ
3470401 - 3470411
2nd stage
kW
Mcal/h
kg/h
1st stage
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
3
kg/dm
2
mm
/s max
• Intermittent (min. 1 stop in 24 hours).
• Two-stage (high and low flame) and single-stage (all - nothing).
kg/h
bar
° C max
number
°C
°C max
dBA
CE
V
Hz
rpm
W
V
A
V1 - V2
I1 - I2
W max
V
Hz
rpm
W
V
A
V1 - V2
I1 - I2
W max
Blast tube
lenght mm
250
385
LIGHT OIL
10.2 (10,200 kcal/kg)
0.82 - 0.85
6 (1.5 °E - 6 cSt)
Boilers: water, steam, diathermic oil
2004/108 - 2006/95 - 92/42 - 2006/42
0036 0382/07
230 - 400 with neutral ~ +/-10%
50 - three-phase
220/240 - 380/415
230 V - 2 x 12 kV
0.2 A - 30 mA
230 - 400 with neutral ~ +/-10%
50 - three-phase
230 V - 2 x 12 kV
0.2 A - 30 mA
2
RL 64 MZ
974 T
391 - 830
336 - 714
33 - 70
206 - 391
177 - 296
17,4 - 33
11.8
107
10 - 20
60
2
0 - 40
60
76
RL 64 MZ
2800
1100
4.7 - 2.7
1800
IP 44
RL 64 MZ
2880
1100
230/400
4.3 - 2.5
1650
IP 44