1.2 Correct use
The DT-Mobil PRO generator tank is an approved
IBC (Intermediate Bulk Container) in accordance
with ADR for hazardous goods in packaging group
III (liquid water-polluting substances).
The filling station is intended for use at a variety of
locations outdoors.
It may only be filled or transported having under-
gone a valid inspection/check. Repeat inspection
2½ years after the date of manufacture according to
ADR 6.5.4.4.1 b) and 6.5.4.4.2. Repeat inspection
5 years after the date of manufacture according to
ADR 6.5.4.4.1 a) and 6.5.4.4.2.
Note: The inspections must be repeated at intervals
of 5 years.
The design; material; production, welding and test-
ing procedures of the steel collecting container
additionally comply with the German steel trough
guidelines (StawaR). The regulations governing fire
prevention and industrial safety must be followed!
Operating temperature range: - 10 °C to + 40 °C
Important!
i
Only a clean medium may be conveyed.
Correct use (preferably) concerns, for example,
the following liquids:
• diesel fuel.
• heating oil.
• biodiesel.
In accordance with the ADR, the following
are required for the simplified transport
of dangerous goods (< 1000 points):
• labelling (sticker) of the filling station.
• requirement to equip with a fire extinguisher
(2 kg)
• carriage of supporting document
(in this case, carriage paper –
observe national exemption regulations)
(no carriage paper in Germany –
exemption 18 S)
• compliance with the so-called "1000-points rule"
in accordance with table 1.1.3.6 ADR, i.e. total
quantity per transport unit < 1000 points.
» 1 l of diesel fuel = 1 point
24
i
Important!
It is essential to read the relevant
regulations of the ADR.
1.2.1 Summary
The equipment is not intended for any other purpose.
For safety reasons, modifications are not allowed to
the filling station (except for the addition of accesso-
ries specifically provided by the manufacturer) – see
section 6. Designated use also includes compliance
with all information in these operating instructions.
1.3 Inappropriate use
i
Important!
Inappropriate use also includes failure to
observe the notices in these operating
instructions.
F u r t h e r m o r e :
• non compliance with the regulations of the ADR
and prevailing national provisions.
• storage and transport of liquids other than those
stipulated under Correct use, e.g.: petrol, bio-
ethanol, chemicals, oils (lubricating, hydraulic,
plant oils).
2. Technical data
2. Technische Daten
DT Mobile PRO
ST 980
Capacity (l)
Dimensions
130x115x130
[cm]:
Weight when
empty [kg]
number of
2 x Flow,
connections
2 x Return
[pcs]
coupling
connecting
external thread
thread
Environmental conditions:
Operating temperature range: - 10 °C to + 40 °C
DT Mobile PRO
PE 980
980
980
130x115x130
470
325
1 x Flow,
1 x Return
G 3/8"
G 3/8"
external thread

Publicidad

loading

Este manual también es adecuado para:

Dt-mobil pro pe 980