4.3
Parameter menu
Code
No.
Name
Password entry
C00
Setpoint and control
C01
source
Load Lenze setting
C02
Lenze 13466184 EDBSL03 v20 EN, DE, FR, IT, ES
Possible Settings
Selection
Lenze
0
0
0
Setpoint source:
0
Analog input (terminal 8; see C34)
1
Code c40
2
Analog input (terminal 8; see C34)
3
LECOM
4
Analog input (terminal 8; see C34)
5
Code c40
6
Analog input (terminal 8; see C34)
7
Code c40
8
Analog input (terminal 8; see C34)
9
Code c40
10 Analog input (terminal 8; see C34)
11 Code c40
Note
• When C01 = 1, 5, 7, 9, or 11, use c40 for speed setpoint
• When C01 = LECOM (3), write speed command to C46
0
No action/loading complete
1
Load 50 Hz Lenze settings
2
Load 60 Hz Lenze settings
3
Load OEM settings (if present)
4
Translate
WARNING!
C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes
CE1...CE3.
NOTE
If an EPM that contains data from a previous software version is installed, C02 =
4 converts the data to the current version.
Commissioning
999
Visible only when password is active
(see C94)
Control configuration:
Control = terminals
Programming = keypad
Monitoring = LECOM
Control = terminals
Programming = LECOM / keypad
Monitoring = LECOM
Control = LECOM
Programming = LECOM / keypad
Monitoring = LECOM
Control = terminals
Programming = remote keypad
Monitoring = remote keypad
Control = remote keypad
Programming = remote keypad
Monitoring = remote keypad
Control = terminals
Programming = Modbus / keypad
Monitoring = Modbus
Control = Modbus
Programming = Modbus / keypad
Monitoring = Modbus
• C02 = 1...4 only possible with
OFF
or
• C02 = 2 : C11, C15 = 60 Hz
IMPORTANT
1nh
13