Power Supplies
SDN 20-24-480CD
Instruction Manual
Dimensions
SOL A
Power Supply
3.43 in
[87.0 mm]
LED Diagnostics
Loss
Low
High
LED
OK
No DC
of AC
AC
Load
Input
Green
---
Amber Green Green Green Green Green
Output Green
---
Green
---
Amber Amber Green
Alarm
---
---
---
Red
Amber
Technical Support
(800) 377-4384 • (847) 268-6651
solahd.technicalservices@emerson.com
www.solahd.com
While every precaution has been taken to ensure accuracy and completeness
in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no
responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Specifications are subject to change
without notice.
P/N: A272-302 Rev. 1 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
Fuentes de Poder
SDN 20-24-480CD
Manual de Instrucciones
Dimensiones
SOL A
Power Supply
3.43 in
[87.0 mm]
Diagnósticos LED
La
CA
Alta
LED
OK
Perdida
No CC
Baja
Carga
de CA
Entrada Verde
---
Ámbar
Verde
Verde
Salida
Verde
---
Verde
---
Ámbar Ámbar
Alarma
---
---
---
Rojo
Ámbar
Soporte técnico
(800) 377-4384 • (847) 268-6651
solahd.technicalservices@emerson.com
www.solahd.com
Aunque se ha tomado toda precaución para asegurar precisión e integridad en
esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna
responsabilidad y deniega toda responsabilidad por daños que resulten por el
uso de esta información o por cualquier error u omisión. Las especificaciones
están sujetas a cambios sin previo aviso.
P/N: A272-302 Rev. 1 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
Input
Nominal Voltage
Inrush Current
Power Factor (PFC)
Nominal Frequency
Output
Nominal Voltage
Current
Power
Power Boost
Hold-up Time
Tolerance
• Line Regulation
5.3 in [134.6 mm]
• Load Regulation
• Time and Temperature Drift
4.98 in [126.6 mm]
Initial Voltage Setting
Ripple
Power Back Immunity
Parallel Operation
Overvoltage Protection
Environmental Data
Ambient Temperature
Degree of Protection
Recommended Minimum
Installation Clearance
Unit Weight
Over-
Too
Certifications
Hot
load
Hot
---
Red
Amber Amber
IECEx
Emissions/Immunity
EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2, EN 61000-3-3;
EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Sag
Immunity
Entrada
Voltaje Nominal
Arranque
Factor de Potencia (PFC)
Frecuencia Nominal
Salida
Voltaje Nominal
Corriente
Potencia
Elevación de Potencia
Tiempo de Retención
Tolerancia
• Regulación de Línea
5.3 in [134.6 mm]
• Regulación de Carga
4.98 in [126.6 mm]
• Desviación de Tiempo y
Temp
Ajuste Inicial de Voltaje
Rizo
Inmunidad de Potencia
Inversa
Operación Paralela
Protección de Sobre Voltaje
Datos Ambientales
Temperatura Ambiente
Grado de Protección
Muy
Sobre-
Cali-
Cali-
Espacio Libre Mínimo
carga
ente
ente
recomendado de Instalación
Unidad de Peso
Verde
Verde
Verde
Certificaciones
Verde
---
Rojo
Ámbar Ámbar
IECEx
Emisiones/Inmmunidad
EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2,
EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4;
EMI F47 Inmmunidad a Picos
Technical Specifications
380–480 Vac, 3Ph
Negligible
Active, > 0.92
50/60 Hz
24 V (Adjustable from 24–28 Vdc)
20 A
480 W
1.5 x nominal current for 4 s
>20 ms (full load, 380 Vac input @ T
amb
95% output voltage
< ± 2% overall
<0.5%
<0.5%
<1%
24.5 V ± 1%
<100 mV
pp
< 35 V: no damage, auto-recovery
Switch selectable
>30.5 Vdc; auto-recovery if <33 Vdc
Storage/Shipment: -40°C to +85°C.
Operating: -40°C to +60°C at full load.
Derate 480 W by 12 W per °C to 360 W from +60°C
to +70°C.
IP20 (EN60529)
1.60 in. (40 mm) above and below; 0.59 in.
(15 mm) left and right. Do not obstruct air flow.
2.86 lb. (1300 g)
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15,
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X
EN60079-0, EN60079-7, EN60079-15
Ex ec nC IIC T4 Gc, IECEx UL15.0017X
IEC60079-0, IEC60079-7, IEC60079-15
Datos Técnicos
380–480 V CA, 3Ph
Despreciable
Activo, > 0,92
50/60 Hz
24 V (Ajustable from 24–28 V CC)
20 A
480 W
1.5 x la corriente nominal por 4 s
>20 ms (carga completa, entrada 380 V CA a
temperatura
mayor a 25°C) al 95% del voltaje
ambiente
de salida
<± 2% en conjunto
<0.5%
<0.5%
<1%
24.5 V ± 1%
<100 mV
pp
< 35 V: no implica daño, autorecuperación
Interruptor seleccionable
>30.5 V CC; recuperación automática si <33 V CC
Almacenamiento/Embarque: -40°C to +85°C
Carga nominal completa: -40°C a +60°C en carga
llena.
Reduzca la capacidad normal de 480 W por 12 W por
el °C a 360 W a partir del +60°C a +70°C.
IP20 (EN60529)
1.60 in. (40 mm) por encima y por debajo; 0.59 in.
(15 mm) izquierda y derecha. No obstruya flujo aéreo.
2.86 lb. (1300 g)
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15,
CAN/CSA 60079-0, CAN/CSA 60079-15
Clase I, Zona 2 AEx nA nC IIC T4 Gc
Clase I, Zona 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X
EN60079-0, EN60079-7, EN60079-15
Ex ec nC IIC T4 Gc, IECEx UL15.0017X
IEC60079-0, IEC60079-7, IEC60079-15
Installation Specifications
Overcurrent Protection
Input: No internal fuses. UL Listed circuit breakers or fuses rated 3 A to 15 A,
480 V are required to be installed for input protection.
Output: Outputs are capable of providing high currents for short periods of
time for inductive load startup.
Relay
N.O. contact rated 200 mA/50 Vdc.
Connections
An accessible disconnect device shall be installed external to the equipment.
Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm
solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6
+25°C) to
mm
) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73
2
N-cm).
Use only one copper wire (60/70°C) per terminal.
Non-ratcheting torque driver recommended.
Safety
The power supply should meet the following conditions for safe use when
installed in a Class I, Zone 2, Groups IIC Hazardous Location:
(1) The equipment shall only be used in an area of not more than pollution
degree 2, as defined in IEC 60664-1.
(2) The equipment shall be installed in an enclosure that provides a degree
of protection not less than IP54 in accordance with IEC 60079-0.
(3) The operating temperature class (T-code) of this device was determined
to be T4.
Warning — Explosion Hazard — Do not disconnect the equipment
while the circuit is live or unless the area is known to be free of ignitable
concentrations.
Warning — Explosion Hazard — Do not open the unit. Do not substitute
components.
Warning — Exposure to some chemicals may degrade the sealing
properties of materials used in the sealed relay device.
The power supplies should meet the following when installed in an ordinary
locations environment: Install in a controlled environment.
DIN Rail Mounting
Simple snap to DIN TS35/7.5 or TS35/15 rail system.
Tilt unit as illustrated.
1.
Put unit onto the DIN rail.
2.
Push unit downward until it stops.
3.
Push at the lower front edge to lock.
4.
Gently shake the unit to ensure that it is secure.
5.
Especificaciones de Instalación
Protección de Sobreintensidad
Entrada: No contiene fusibles internos. Para protección de entrada se
requiere instalar interruptores de circuito o fusibles certificados por UL con
valoración de 3 A a 15 A a 480 V.
Salida: Las tomas de salida son capaces de entregar corrientes elevadas
durante lapsos breves para el arranque de cargas inductivas.
Relevo
N.O. contacto valoró 200 mA/50 V CC.
Conexiones
Un dispositivo accesible de desconexión debe ser instalado externamente
al equipo.
Entrada: terminales tipo tornillo Rango de tamaños de conectores:
1,5–6 mm
para conductores unifilares o trenzados. Torque de tornillo:
2
50-73 N-cm
Salida: dos terminales por salida. Rango de tamaños de conectores:
1,5–6 mm
para conductores unifilares o trenzados. Torque de tornillo:
2
50-73 N-cm
Utilizar solo un cable de cobre (60/70 °C) por terminal.
Se recomienda un conductor de torque sin ajuste.
Seguridad
Las siguientes condiciones son requeridas para uso seguro de la fuente de
poder cuando la instalación es en áreas clasificadas como Clase I, Zona 2,
Grupo IIC de Ubicación Peligrosa:
(1) El equipo debe ser usado sólo en un área de no más de un grado 2 de
contaminación, tal como se define en la norma IEC 60664-1.
(2) El equipo debe instalarse en el interior de un recinto que proporciona
un grado de protección no inferior a IP54 de acuerdo con la norma IEC
60079-0.
(3) El código de temperatura (T-code) de operación de este equipo es de
clase T4.
Advertencia — Peligro de Explosión — No desconecte el equipo
si el circuito está conectado, exceptuando si se sabe que no existen
concentraciones inflamables en el área.
Advertencia — Peligro de Explosión — No abra la unidad. No substituya
componentes.
Advertencia — La exposición a ciertas sustancias químicas podría
degradar las propiedades selladoras de los materiales utilizados en el relé
sellado del equipo.
Las fuentes de alimentación deben cumplir con lo siguiente cuando
se instalen en un entorno de áreas ordinarias: instalar en un entorno
controlado.
Montaje en Riel DIN
Ajuste simple según DIN TS35 / 7.5 o TS35 / 15.
1. Incline la unidad como se ilustra.
2. Póngala sobre el Riel DIN.
3. Empuje hacia abajo hasta que se detenga.
4. Empuje de la parte baja del frente para asegurar.
5. Mueva la unidad ligeramente para verificar está segura.
) for
2