Drive Parameters
Display Parameters
(Read Only)
Units /
No.
Name
Default
d-00 Command Frequency
0.1 Hz 0 - 240.0
d-01 Output Frequency
0.1 Hz 0 - 240.0
d-02 Output Current
0.1 A 0 - 200 (% of rated current)
d-03 Bus Voltage
1 V
0 - 1000
d-04 Fault Code
Annn alphanumeric code
d-05 Input Status
decimal 0000 - 7111
d-06 Drive Rating
decimal
d-07 Firmware Version
Annn alphanumeric code
d-08 Analog Input 1 Units
0.1 % 0 - 110.0
d-09 Analog Input 2 Units
0.1 % 0 - 110.0
Program Parameters
(Parameters that can be programmed only while the drive
is stopped are indicated by an asterisk *)
Units /
No.
Name
Default
Group 0: Protection
P-00 Minimum Speed *
0 Hz
P-01 Maximum Speed *
60 Hz Minimum Speed - 240
P-02 Motor Overload Current
x.x A
P-03 Reverse Disable *
0
P-04 Auto Restart Attempts
0
P-05 Current Limit
150 % 10% - 150% of drive's rated current x x x
Group 1: Digital Input / Output
P-10 Start Control *
2
P-11 Configurable Input *
2 (A)
1 (B)
0 (C)
Drive Parameters
Model
Range
A B C
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x
Model
Range
A B C
0 - Maximum Speed
x x x
x x x
20% - 200% of drive's rated current x x x
0 = reverse enabled
x x x
1 = reverse disabled
0 - 10
x x x
1 = keypad control
x
x
2 = 2-wire control
x
x
3 = 3-wire control
x
x
0 = function loss (P-10 ≠ 3)
1 = disabled
x
1 = preset
x
1 = reverse run (2-wire)
2 = jog (P-10 ≠ 1)
x x
2 = jog (P-10 ≠ 1 or 3)
3 = alternate spd ref select
x x
3 = alt spd ref select (P-10 ≠ 3)
4 = n.c. coast-to-stop
x x
4 = n.c. coast-to-stop (P-10 ≠ 3)
5 = secondary accel/decel
x x
5 = sec accel/decel (P-10 ≠ 3)
11
x
x
x
x
x
x
x
x
x
x
x