Rockwell Automation SP200 Manual De Instrucciones página 24

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 91
Compliance with EU Requirements
The SP200 drive is CE-marked for Low Voltage (LV) Directive 73/23/EEC and all
applicable standards when installed as described within the Low Voltage section that
follows. It also has been tested to meet Electromagnetic Compatibility (EMC) Directive
89/336/EEC when installed as described within the Electromagnetic Compatibility
section that follows. Contact the Rockwell AutoFax service in the United States at
216-646-7777 (or your local Rockwell Automation office if outside the U.S.) for copies of
the Declaration of Conformity (DOC).
Conformity of the SP200 drive to EU directives does not guarantee that the entire
system will conform. For EMC, many other factors can affect the total installation, and
only direct measurements can verify total conformity. It is the responsibility of the
machine manufacturer (or end user, if the machine is being modified or used beyond
manufacturer's specifications) to comply.
Low Voltage Directive 72/23/EEC
• Follow all general precautions and ATTENTION statements throughout this manual.
• Provide an earth ground connection to the PE terminal.
• Install in a protective enclosure which restricts access to IP 20 rated devices as
required by your national and local codes and regulatory agencies.
Electromagnetic Compatibility Directive 89/336/EEC
• Install the SP200 drive and Input Mains Filter (see the table below) in a typical IEC or
NEMA metal (shielded) enclosure as shown in the figure on the following page.
Adhere to maximum motor cable lengths as specified on page 7 ( ≤ 25 m).
Drive Model
Number
Filter Model Number
S20-X02P3.....
S20-MF1-Y014
S20-X04P2.....
S20-MF1-Y014
S20-X06P0.....
S20-MF1-Y014
S20-Y07P0.....
S20-MF1-Y014
S20-202P3.....
S20-MF1-45P0
Refer to SP200 Mains Filters (D2-3420) for filter dimensions and weights.
• Keep all input power, output power, and control signal wiring, both inside and outside
enclosure, physically separate from one another.
• Connect the enclosure to the SP200 PE input (top) terminal.
• Connect the enclosure to earth ground.
• Use shielded cable with a ground conductor or individual conductors in grounded
metal conduit for motor power wiring on the output side of the drive, both inside and
outside the enclosure, all the way to the motor. Bring the shield as close to the output
power terminals as possible. Connect the motor cable ground and shield to the
ground terminal on the output (bottom) side of the SP200 drive. Connect the
opposite end of the motor cable ground conductor and shield to the motor housing.
• Use shielded cable or grounded metal conduit for control wiring both inside and
outside the enclosure, all the way to the control source. Bring the shield as close to
the control terminals as possible. Connect the shield to the SP200 shield/common
(terminal 1) and to the PE terminal on the input side (top) of the SP200 drive. Also
connect the opposite end of the shield to the common of the device that is controlling
the SP200 drive.
• Use EMC-tested 360 degree cable clamps to connect the motor and control shields
to the enclosure cable exit point(s) and to the motor housing. Contact points must be
clean and free of paint or nonconductive coating.
• Make certain all ground connections provide a low impedance path for high
frequency signals.
14
Drive Model
Number
Filter Model Number
S20-204P2.....
S20-MF1-45P0
S20-207P0.....
S20-MF1-49P5
S20-401P3.....
S20-MF1-45P0
S20-402P0.....
S20-MF1-45P0
S20-402P3.....
S20-MF1-45P0
SP200 AC Drive Quick Start Guide

Publicidad

Tabla de contenido
loading

Tabla de contenido