Technical Specifications
AC
Input
AC Input
Output
Current
1
Voltage
Voltage
HP
(Amps)
100-120,
230,
0.5
9.4
1-phase
3-phase
1.0
17.2
1.5
24.6
200-240,
230,
0.5
4.7
1-phase
3-phase
1.0
8.6
1.5
12.3
2.0
14.3
200-240,
230,
0.5
2.7
3-phase
3-phase
1.0
5.0
2.0
8.3
380-460,
460,
0.5
1.5
3-phase
3-phase
1.0
2.4
2.0
4.1
1
The input voltage range has a tolerance of ±10%, 47 to 63 Hz.
2
Recommended fuse type: UL Class J or CC, 600 V, time delay.
3
Device must meet UL 489 for UL purposes.
Control Inputs
• Rated voltage: 10 VDC to 24 VDC (±10%)
• Load (each): 10 mA minimum, 20 mA maximum
• Maximum allowable off-state leakage current: 1.5 V / 2.0 mA
Speed Reference Input
• Analog input impedance: 0 to 10 V: ≥100 kΩ
4 to 20 mA input: ~250 Ω
Relay Output
• Rated current and voltage: 0.5 A maximum at 125 VAC
1.0 A maximum at 30 VDC
Operating Performance
• Input frequency resolution: 0.4% analog, 0.1 Hz digital
• Output frequency resolution: 0.1%
• Output voltage regulation: 3%
• Power dip control ride through time: 100 msec minimum
Ambient Conditions
°
°
• Operating temperature: 0 to 50
C (32
°
°
• Storage temperature: -40
C to 85
C (-40
• Humidity: 0 to 95% non-condensing
• Elevation: 1000 meters (3300 ft) maximum without derating. For every 91.4 meters
(300 ft) above 1000 meters, derate the current by 1%. Above 3000 meters,
(10,000 ft), consult your Reliance Electric Sales Office.
2
Fuse
Circuit
Output
Typical
2
Breaker
Current
Rating
Power
3
(Amps)
(Amps)
Rating
(A)
Loss (W)
2.3
15 or 16
15
25
4.2
30
30
45
6.0
40
40
70
2.3
10
10
25
4.2
15 or 16
15
45
6.0
20
20
70
7.0
25
25
75
2.3
6
5
25
4.2
10
7
40
7.0
15 or 16
15
70
1.3
3 or 4
3
25
2.0
6
4
30
3.5
10
7
50
°
F to 122
F)
°
°
F to 185
F)
SP200 AC Drive Quick Start Guide