Installation and Connection
NOTE!
To use the analog inputs and/or outputs with signal in current, you must set
switch S1 and related parameters as per
information, refer to the MW500 programming manual.
To modify the digital inputs from active low to active high, check the use of
parameter P0271 in the MW500 programming manual.
Table 3.1: Configuration of the switches to select the type of analog input and output signal on the CFW500-IOS
Input/
Signal
Output
Voltage
AI1
Current
Voltage
AO1
Current
NOTE!
Configuration to connect the RS485:
S1.3 = ON and S1.4 = ON: terminal RS485 ON.
S1.3 = OFF and S1.4 = OFF: terminal RS485 OFF.
Any other combination of the switches is not allowed.
For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the plug-in module connector with shielded cables separated from the other wiring
(power, command in 110 V / 220 Vac, etc.), according to
on page
17. If those cables must cross other cables, it must be done perpendicularly,
keeping the minimum separation distance of 5 cm (1.97 in) at the crossing point.
Connect the shield according to the figure below:
16 | MW500
Setting of
Signal
Switch S1
Range
S1.1 = OFF
0...10 V
0...20 mA
S1.1 = ON
4...20 mA
S1.2 = ON
0...10 V
0...20 mA
S1.2 = OFF
4...20 mA
Inverter
side
Figure 3.5: Connection of the shield
Table 3.1 on page
Parameter Setting
P0233 = 0 (direct reference) or 2 (inverse reference)
P0233 = 0 (direct reference) or 2 (inverse reference)
P0233 = 1 (direct reference) or 3 (inverse reference)
P0253 = 0 (direct reference) or 3 (inverse reference)
P0253 = 1 (direct reference) or 4 (inverse reference)
P0253 = 2 (direct reference) or 5 (inverse reference)
Item 3.2.7 Cable Separation Distance
Insulate with tape
Do not ground
16. For further