Control Board; Control Connections - WEG MW500 Serie Manual Del Usuario

Ocultar thumbs Ver también para MW500 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.2.5 Control Board

Plug-in modules are connected to control board. S10 DIP-switch are available in control board,
for more information refer to

3.2.6 Control Connections

The control connections (analog input/output, digital input/output and interface RS485) must
be performed according to the specification of the connector of the plug-in module connected
to the MW500. Refer to the guide of the plug-in module in print. The typical functions and
connections for the CFW500-IOS standard plug-in module are shown in
15. For further details about the specifications of the connector signals, refer to
TECHNICAL SPECIFICATIONS on page
(*) Digital input 2 (DI2) can also be used as input in frequency (FI). For further details refer to the programming manual of the MW500.
(**) For further information, refer to the detailed specification in
Figure 3.4: Signals of the connector of the CFW500-IOS plug-in module
The location of the plug-in module and DIP-switches to select the type of analog input and
output signal and the termination of the RS485 network is shown in
The MW500 inverters are supplied with the digital inputs configured as active low (NPN), analog
input and output configured for signal in voltage 0...10 V and with the termination resistor of
the RS485 OFF.
Section 4.3 OPERATING MODES OF THE HMIR on page
36.
Section 8.2 ELECTRONICS/GENERAL DATA on page
Installation and Connection
Figure 3.4 on page
Connector
Description
1
DI1
Digital input 1
3
DI2
Digital input 2
5
DI3
Digital input 3
7
DI4
Digital input 4
9
+ 24 V
Power supply + 24 Vdc
Digital output 1
11
DO1-RL-NO
(Relay NO contact 1)
Digital output 1
13
DO1-RL-C
(Relay common point 1)
Digital output 1
15
DO1-RL-NC
(Relay NC contact 1)
2
AO1
Analog output 1
4
GND
Reference 0 V
6
AI1
Analog input 1
Reference + 10 Vdc for
8
+ 10 V
potentiometer
10
DO2-TR
Digital output 2 (Transistor)
12
RS485 - A
RS485 (Terminal A)
14
RS485 - B
RS485 (Terminal B)
16
GND
Reference 0 V
37.
Figure A.1 on page
21.
Chapter 8
(**)
(*)
123.
MW500 | 15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mw500