Descargar Imprimir esta página

Siemens PolyCool CPS 40 Manual De Instalación página 37

Ocultar thumbs Ver también para PolyCool CPS 40:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Picture Function Parameter
1)
4
REFRIG
Refrigerant type REFRIG R22, R23, R32, R125,
2)
5
ENABLE
Enable/disable
compressor and
EIV feedback
4)
6
CAP
Application
7
SENSOR Sensor 1
Sensor 2
Sensor 3
Siemens
Building Technologies
In this mode, you enter the refrigerant used in your plant.
Additionally, it is possible to select the units of pressure,
temperature and EIV. You can also configure the types of sensors
according to your specific application.
An incorrect entry for the refrigerant can damage your plant!
Optionally, it is possible to configure the control of the cooling
capacity (refer to chapter 6). The controller by default comes with
capacity control deactivated.
Code
COMP
3)
Fb
-
X1
X2
X3
CPS40
Adjustable range/
increment
R134a, R152a, R170,
R227E, R236F, R245F,
R290, R401A, R401B,
R401C, R402A, R402B,
R404A, R406A, R407A,
R407B, R407C,R407F,
R408A, R409A, R410A,
R410B, R413A, R417A,
R421A, R422A, R422D,
R427A, R434A, R437A,
R438A, R502, R507, R600,
R600a, R717, R723, R744,
R1270
ON (for C1)
ON/OFF
NO = simple superheat
(Application 1)
EXT = External capacity
control (Application 2)
INT = Internal capacity
control (Application 3)
QBE9101-P10U with 4...20
mA output
Ni1000
0...10 V, 4...20 mA
CE1U3372XX / H 74 319 0555 0 d
Setting
Procedure
Default
NA
Set with +/-
Confirm
with <OK>
Exit with
<ESC>
ON
OFF
NO
-
Ni1000
0...10 V
37/136
2013-10-01

Hide quick links:

Publicidad

loading