BIP LD2-T_ _ _-03-S75
Inductive Positioning System
6
IO-Link interface (continued)
6.7
System commands
Index
Subindex
Hex
Dec Hex Dec
0002 2
00
0
Tab. 6-7:
System commands
6.8
Teach-in of the measuring range
The start and end points of the curve (Slmin and Slmax)
can be defined by teaching in to indicate the gradient
progress and gradient value of the curve.
Teach-in process of the measuring range
1. Activate the measuring range settings.
2. Move target to new Slmin.
3. Temporarily saves the current position as Slmin.
4. Move target to new Slmax.
5. Temporarily save the current position as SImax.
6. Apply and activate values for the new measuring range Slmin/
Slmax.
3)
Within the original linear range
14
english
Parameters Data
Access
format
System
UINT8
Write only 0x82
command
3)
3)
Value
Comments
range
Reset
0xE0
Teaching linearity
range
0xE1
Slmin
0xE2
Slmax
0xEA
Enable linearity
range
0xEB
Inversion
0xEE
Reset linearity
range
0xEF
Clear Teach-in
0xA5
Reset
maintenance
If the target leaves the measuring range
during teaching, the error message
TEACH_STATE_ERROR is reported.
Index
Subindex Access
Hex
Dec
Hex Dec
0002 2
00
0
Write only
0002 2
00
0
Write only
0002 2
00
0
Write only
0002 2
00
0
Write only
Reset to factory settings
Stores the new linearity
range
Store teach-in start position
Store teach-in end position
Enables Linear Teach-in
Mode
Inverts the sensor output
Reset linearity range to
factory default settings
Clear running Teach-
in-process
Reset maintenance
Value
0xEA
0xE1
0xE2
0xE0