Key
KR/KG
2.2 Displays
2.2.1
Multifunctional display
The multifunctional display operates in four different modes, which are selectable by means of the
"MODE" pushbutton and shown by the related indicator light ("MODE1".."MODE4"). If the
selected mode includes multiple pages, they may be (cyclically) selected by means of the
pushbutton.
The display backlight is controlled by the card, which turns it off if no pushbutton is pressed within 30
seconds. Press any pushbutton to light it again. The ON time ("LAMP SAVER") can be set by the user.
However, the light is always OFF while the engine is starting.
MODE 1
2.2.1.1
This mode includes two pages. The first page displays the typical readings for the generator (delta
voltages, currents, frequency for each phase in turn) and for the engine (lubricating oil pressure,
cooling water temperature, and engine speed), if available; active faults, if any, and the engine
conditions during the starting, cooling, and stopping phases are also displayed. The second page
displays the three voltages and three currents simultaneously.
If there is a fault, it can be hidden by pressing the
can be displayed. When changing mode, the last selected page will be displayed when returning to
"MODE 1".
MODE 2
2.2.1.2
Information on power values and the power supplied by the system, besides the mains delta voltages,
are displayed in this mode on multiple pages. By pressing the
scroll through the various pages. When changing mode, the last selected page will be displayed when
returning to "MODE 2".
MODE 3
2.2.1.3
This mode displays the main meters (starting operations, total and partial operating hours, operating
hours under load), the remaining time before maintenance, the battery voltage, as well as the auxiliary
current, the fuel level and additional information from the CANbus (see section 0) by means of multiple
pages which are selectable by pressing the
selected page will be displayed when returning to "MODE 3".
MODE 4
2.2.1.4
This mode includes some pages showing card information (clock/calendar, internal temperature, the
card serial number, total operating hours), control of the fuel pump (see section 6) as well as a page
showing the status of serial port. A few additional pages relating to the engine and CANbus
communication diagnostics are also displayed (see section 0). By pressing the
pushbutton it is possible to scroll through the various pages. When changing mode, the last selected
page will be displayed when returning to "MODE 4".
6
User's Manual DST4400
Function
In manual (or "TEST") mode it is used to switchover the devices between the generator and
the mains (switching over to the mains is always possible; switching over to the generator is
possible only if the relative electrical values are within tolerance).
"VIEW" pushbutton so that the engine readings
"VIEW" pushbutton it is possible to
"VIEW" pushbutton. When changing mode, the last
"VIEW"
"VIEW"