The maximum number of saved events is 99, after that the least recent event is overwritten.
To exit log display, press the
5.
Selecting the language
To select a different language, turn the card on while pressing the
(selector in the OFF/RESET position) until the display shows the following message:
Special Function
Func: [LANGUAGE]
Press the
the
beginning of the procedure, it is necessary to press the pushbutton
6.
Fuel pump
The fuel pump is controlled by a page of MENU 4, which is displayed only if the device is configured to
drive the pump. This page shows the (on/off) status of the pump and the operation mode (on/off
manual or automatic). The pump is started/stopped by holding down the
second:
o
In MAN-OFF mode, the pump is started by forcing the MAN-ON mode.
o
In MAN-ON mode, the pump is stopped by forcing the MAN-OFF mode.
o
In AUTO mode, the pump is stopped or started only if it is in hysteresis (it is not possible to start the
pump if the level is too high, and it is not it is not possible to stop it if the level is too low).
Also in this window, the pump mode can be changed cyclically between the three possible settings
listed above by holding down the
ATTENTION: In order to select the pump operation mode it is necessary to hold down the indicated
or
displayed page.
The "J208 7" input on the card is set only for the fuel low level alarm in the external tank. It is active if
connected to the generator's ground.
"VIEW" pushbutton.
and the vertical scroll pushbuttons to select "LANGUAGE", then confirm by pressing
pushbutton (even if "LANGUAGE" is already displayed within square brackets at the
pushbutton for at least one second; holding them for a shorter time only changes the
pushbutton for one second.
and
pushbuttons
twice). PASSWORD: "1"
pushbutton for 1
User's Manual DST4400
9