ENGLISH

8. Configuration

Always switch OFF all DC and AC power sources to activate new dipswitch settings.
DIP switch functions
AC output voltage setting
Output voltage
230 V
240 V
AC input transfer system
Mode
0
1
(Sensitive loads)
* AC output voltage setting
** AC output frequency setting is 60Hz
AC output frequency setting
Frequency
50 Hz
60 Hz
1
AC output voltage setting
2
AC input transfer system
3
AC output frequency setting
4
Power saving or Master/Slave setting
5
Power saving or Master/Slave setting
6
Power saving or Master/Slave setting
7
Power saving mode or Master/Slave mode
8
LCM remote or DIP switch control
DIP switch 1
0
1
Inverter- to Bypass mode
when AC input is in the
range of:
230V* +/-12%
230V* +/-12%
and
47~57Hz (53~63Hz)**
Bypass- to Inverter mode
when AC input is out of
range of:
230V* +12%, -25%
230V* +12%, -25%
46~58Hz (52~64Hz)**
DIP switch 3
0
1
or
DIP switch 2
0
1