Installation; General Instructions; Place Of Installation - Lamborghini Caloreclima Reply 51 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2. Installation

2.1 General Instructions

THE BOILER MUST ONLY BE INSTALLED BY QUALIFIED PERSONNEL, IN COMPLIANCE WITH ALL THE IN-
STRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE NATIONAL AND
LOCAL REGULATIONS, AND THE RULES OF PROPER WORKMANSHIP.
Reply 51 - 71 - 101 is a high-efficiency heat generator arranged to operate alone or in cascade (bank). When two or
more generators Reply 51 - 71 - 101 are installed in cascade with the original kits Lamborghini, respecting the prescrip-
tions of this manual, they can be considered as a single heat generator of total power equal to the sum of the powers
of all the units connected in cascade.
All the requirements of the current standards and regulations applicable to this "equivalent" generator with total heating
capacity must be met. In particular the place of installation, safety devices and fume exhaust system must be adequate
for the total heating capacity of the bank of units.
In fact, each Reply 51 - 71 - 101 is a complete and independent heat generator, equipped with its own safety devices.
In case of overtemperature, a lack of water or no circulation in the unit, the protection devices cause the unit to switch
off or shut down, preventing it from working.
The installation instructions given in the following paragraphs concern both single units and connection in cascade.

2.2 Place of installation

The generator can be installed directly outside or in a special room with ventilation openings to the outside as prescribed
by current regulations. If there are several burners or extraction units that can work together in the same room, the ven-
tilation openings must be sized for simultaneous operation of all the units. The place of installation must be free of flam-
mable objects or materials, corrosive gases, volatile substances or dusts. For positioning, leave enough space around
the modules for normal maintenance operations. Make sure the front door opens without hindrances.
B
The air necessary for combustion enters through special openings in the bottom and top part of the appliance.
Make sure these air passages are not obstructed in any way.
58
fig. 15 - Air inlet
cod. 3540H322 - 09/2008 (Rev. 01)