Test Run (Fig. 6-1) - Mitsubishi Electric City Multi PLFY-P-VCM-E Serie Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34
5. Installing the grille
A
Fig. 5-11

6. Test run (Fig. 6-1)

CENTRALLY CONTROLLED
CHECK
˚C
STAND BY
DEFROST
TEMP.
2
TIMER SET
PAR-20MAA
Fig. 6-1
Fig. 6-2
D
B
C
BC
D
1Hr.
ON OFF
˚C
CLOCK
FILTER
CHECK MODE
E
TEST RUN
ERROR CODE
NOT AVAILABLE
FUNCTION
A
ON/OFF
5
FILTER
CHECK TEST
1
3
4
A Insert the pump end 3 to 5 cm
B Cover of water supply inlet
C About 1000 cc
D Water
E Drain plug
5.5. Installing the intake grille (Fig. 5-11)
• Perform the procedure that is described in "5.2 Preparing to attach the grille" in
reverse order to install the intake grille and the corner panel.
A Refrigerant piping of the main unit
B Drain piping of the main unit
C Corner panel
* Installation in any position is possible.
D Position of the levers on the intake grille when sent from the factory.
* Although the clips can be installed in any of four positions.
5.6. Check
• Make sure that there is no gap between the unit and the grille, or between the grille
and the surface of the ceiling. If there is any gap between the unit and the grille, or
between the grille and the surface of the ceiling, it may cause dew to collect.
• Make sure that the wires have been securely connected.
1 Press [TEST RUN] button twice → displaying [TEST RUN] on the screen.
2 Press [Selecting operation] button. → Check that wind is blowing out.
3 Press [Fan speed adjustment] button. → Check that the wind speed is changed.
4 Press [Up/down airflow selection] button to change wind direction.
5 Press [ON/OFF] button to clear test run. → Test run stops.
A Lighting in operation
B Displaying inspection code
C Displaying remaining test run time
D Displaying indoor unit's liquid pipe temperature
E Displaying test run
Note:
• The 2-hour-set timer is activated to automatically stop test run after two hours.
• The remote controller displays the temperature of the indoor unit's liquid
pipe on the temperature display section during test run.
6.1. Check of drainage (Fig. 6-2)
• During the trial run, ensure the water is being properly drained out and that no
water is leaking from joints.
• Always check this during installation even if the unit is not required to provide cool-
ing/drying at that time.
• Similarly, check the drainage before finishing ceiling installation in a new premises.
(1) Remove the cover of the water supply inlet and add about 1000 cc of water using
a water supply pump etc. During this process, be careful not to spray water into
the drain pump mechanism.
(2) Confirm that water is being drained out through the drainage outlet, after switch-
ing over from remote control mode to trial run mode.
(3) After checking the drainage, ensure that the cover is replaced and the power
supply is isolated.
(4) After confirming the drainage system is functioning, replace the drain plug.