Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The 36J22/24/54/55 combination gas valves are de-
signed for direct spark ignition (DSI) and hot surface
ignition (HSI) system applications. These valves
are equipped with redundant and main solenoid
valves that control gas flow to the main burners, a
pressure regulator and a two-position on/off switch
for regulation and electrical shut-off of the solenoid
valves. The 36J24 and 36J55 are also equipped
with a slow-opening pressure regulator for softer
lighting characteristics. When the second solenoid
on 2-stage valves is energized the valve operates
at the second stage (high) outlet pressure setting.
Model
Coil
Number
Voltage
36J22
24V
36J24
24V
36J54
24V
36J55
24V
Pressure Regulator Adjustment Range (in W.C.)
Gas
Single
Type
Stage
Natural 2.5 – 5.0 1.0 – 4.0 2.0 – 5.0
LP
7.0 – 12.0 4.0 – 10.0 6.0 – 12.0
CONTENTS
Description ........................................................ 1
Specifications .................................................... 1
Precautions ....................................................... 2
Installation
System Wiring ...................................... 3
Adjustment
Pressure Regulator Adjustment ............ 7
Lighting Instructions ..........................................
Contents French
................................................ 9
Contents Spanish
............................................ 17
36J22, 36J24, 36J54 and 36J55
Stages
Characteristics
1
1
2
2
Two Stage
Min. Diff.
Low
High
Low to High
www.white-rodgers.com
www.emersonclimate.com
DSI and HSI Single and Two Stage
Combination Gas Valves
INSTALLATION INSTRUCTIONS
36J Single Stage
Opening
Intermittent Pilot
Proven Pilot
Fast
Slow
Fast
Slow
Pipe Sizes
Available
(inches)
1
1 /2" x 1 /2" NPT
2
Type of Gas: Natural gas
Ambient Temperature: -40° to 175°F
Pressure Rating: 14" W.C. (½ PSI) max.
Voltage: 24 VAC
Frequency: 50/60 Hz
Current: Single Stage – 0.28A
8
Mounting Positions: Multipoise – Control may
DESCRIPTION
Fig. 1
HSI
No
Yes
No
Yes
No
Yes
No
Yes
SPECIFICATIONS
PIPE SIZES/CAPACITIES
Capacity (BTU/hr) at
1" pressure drop across valve
AGA Std. Nat. Gas
(1,000 BTU/cu. ft.)
140,000
LP gas (use conversion kit)
Two-Stage – 0.43A
be mounted in any position
PART NO. 37-7338B
36J Two-Stage
Standing
DSI
Pilot
Yes
No
Yes
No
Yes
No
Yes
No
LP Gas
(2,500 BTU/cu. ft.)
226,800
Replaces 37-7338A
1346