3.3.5
Mounting the weather cover
► Illustration on the fold-out page (Figure D)
Fasten the weather cover to the flame detector with the spring
washers and screws using a 3/16" hex key.
3.3.6
Orienting the flame detector
► Illustration on the fold-out page (Figure C)
1. Release the locking screws (C-4, C-5) using a 3/16" hex key so
that the flame detector can be rotated.
2. Point the flame detector towards the protected area and make
certain that the view of the area is unobstructed.
3. Secure the flame detector in that position by tightening the locking
screws (C-4, C-5) on the tilt mount using a 3/16" hex key.
3.3.7

Reprogramming the configuration

The factory default configuration is as follows:
Function
Sensitivity level
Alarm Delay
Alarm Latch
Automatic BIT
Alarm BIT
Default value for
15
30
40
A
A
A
no
no
no
yes
yes
-
no
no
-
Function
Heat Mode
Temperature
RS-485 address
1)
Auxiliary BIT
1)
EOL
1)
Auxiliary Relay
1)
only available in wiring option 4 and 5
30
A
no
yes
no
Default value for
auto
auto
auto
5 °C
5 °C
5 °C
(41 °F)
(41 °F)
(41 °F)
1
1
1
no
no
-
no
no
no
no
no
no
en
Use
auto
5 °C
(41 °F)
1
no
no
no
13