Technical Data - Endress+Hauser RIA 450 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 94
Process display

8. Technical data

General
Unit function
information
Application
Process display,
limit contactor
Operating and
Measurement
system
principle
construction
Measurement
system
Input
Input types
Measurement
range
(Input current/
coltage)
Measurement
range (option
"Universal input")
Integration time
Output
Output signal
(loop power
supply)
Number
Output (relays)
Output signal
Number
Contact type
Contact loading
58
Process display for panel mounting.
The display recieves an anlogue signal and shows the
corresponding value on the display.
Four presettable set points monitor the measured
value for any infringement of the preset conditions and
control the relays. Transmitters connected can be
directly powered by the unit.
The analogue signal connected is digitalised, analysed
and indicated in the display.
Microcontroller controlled display with LC display,
analogue input, limit relays and loop power supply.
Current, voltage, resistive thermometers (RTD),
thermocouple (TC).
Voltage:
0...1/10 V; max. 50 V
Current:
0/4...20 mA; max.100 mA
Voltage:
+/-20 mV, +/-50 mA, ±100 mV, ±200 mV,
±1 V, ±2 V, ±5 V, ±10 V, 0...1 V, 0...10 V,
max. ±50 V, Ri: 1 MOhm
Current:
0/4...20 mA; max.100 mA
RTD:
Pt100, Pt500, Pt1000:
-100°C ... +600°C (DIN EN60751);
Ni100: -60°C...+180°C (DIN 43760);
Sensor current: approx. 1 mA; connection: 2-, 3-wire;
Cable compensation: To approx. 100 Ohm
TC: Type T: -270...+400°C
Type K: -270...+1372°C
Type S:
0...+1800°C
Type N: -270...+1300°C Type U: -200...+60°C
Type L:
Type T, J, K, S, B, N to DIN EN60584;
Type U, L to DIN 43710;with cable open circuit monitor
200 ms
24 V +/- 10%, 25 mA (internal limit, short circuit
protected)
Option: 100 mA, without short circuit protection
1
Binary, switches on reaching the set point
4
1 potential free changeover contact
<= 250 VAC, 3A / 30 VDC, 3A
Ri:1 MOhm
Ri: 50 Ohm
Ri: 50 Ohm
Type J: - 210...+1200°C
Type R:
-50...+1800°C
Type B: 200... +1820°C
-200...+900°C