Dräger VarioGard Instrucciones De Uso página 33

Ocultar thumbs Ver también para VarioGard:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 78
transmitter
Actual value alarm A1
Alarm threshold
120 ppm
Hysteresis
Actual value alarm A2
Alarm threshold
120 ppm
Hysteresis
Actual value alarm A3
Alarm threshold
120 ppm
Hysteresis
Actual value alarm A4
Alarm threshold
120 ppm
Hysteresis
Mean value alarm A1
Alarm threshold
Hysteresis
Mean value alarm A2
Alarm threshold
Hysteresis
Mean value alarm A3
Alarm threshold
Hysteresis
Mean value alarm A4
Alarm threshold
Hysteresis
Hysteresis of e.g. 10 ppm with a limit of e.g. 100 ppm means that the alarm is set at 100 ppm and reset if the value falls below 90 ppm.
1)
Presetting according to VDI 2053 (2004)
2)
For VarioGard 3200 CAT and VarioGard 3300 IR Ex
Dräger VarioGard
CO
NH
-sensor
O
3
2
1)
50 ppm
20 % by vol.
5 ppm
5 ppm
0.2 vol.-%
200 ppm
19 vol.-%
5 ppm
20 ppm
0.2 vol.-%
500 ppm
18 vol.-%
5 ppm
50 ppm
0.2 vol.-%
1000 ppm
17 vol.-%
5 ppm
100 ppm
0.2 vol.-%
20 ppm
1200 ppm
0 vol.-%
4 ppm
0 ppm
0 vol.-%
40 ppm
1200 ppm
0 vol.-%
8 ppm
0 ppm
0 vol.-%
60 ppm
1200 ppm
0 vol.-%
10 ppm
0 ppm
0 vol.-%
60 ppm
1200 ppm
0 vol.-%
10 ppm
0 ppm
0 vol.-%
-sensor
NO
NO
-sensor CH
2
transmitter
10 ppm
1 ppm
3 ppm
0.1 ppm
15 ppm
2 ppm
3 ppm
0.2 ppm
20 ppm
3 ppm
3 ppm
0.3 ppm
20 ppm
5 ppm
3 ppm
0.5 ppm
50 ppm
1 ppm
5 ppm
0.1 ppm
50 ppm
2 ppm
5 ppm
0.2 ppm
50 ppm
3 ppm
5 ppm
0.3 ppm
50 ppm
5 ppm
5 ppm
0.5 ppm
Configuration
2)
LPG
CO
-sensor
4
2)
sensor
10 %LEL
10 %LEL
0.5 vol.-%
5 %LEL
5 %LEL
20 %LEL
20 %LEL
5 %LEL
5 %LEL
40 %LEL
40 %LEL
5 %LEL
5 %LEL
40 %LEL
40 %LEL
5 %LEL
5 %LEL
40 %LEL
40 %LEL
3 %LEL
3 %LEL
80 %LEL
80 %LEL
3 %LEL
3 %LEL
100 %LEL
100 %LEL
3 %LEL
3 %LEL
100 %LEL
100 %LEL
3 %LEL
3 %LEL
-sensor
2
500 ppm
1 vol.-%
500 ppm
2 vol.-%
500 ppm
3 vol.-%
500 ppm
1 vol.-%
500 ppm
1 vol.-%
500 ppm
3 vol.-%
500 ppm
3 vol.-%
500 ppm
33

Publicidad

Tabla de contenido
loading

Tabla de contenido