2. PRODUCT PRESENTATION
Fan casing manufactured from heavy gauge galvanized steel sheet.
Circular duct connection flanges with integrated rubber air seal.
Single inlet fan.
In line horizontal discharge.
Standard version, 25mm thickness of fireproof fiberglass insulation version (50mm thickness of
fireproof fiberglass insulation version on request).
Possibility to be equipped with a G4 filter.
Motors:
o CAB-PLUS 125 and 160: IP44 motor with single-phase external rotor 230V, 50 Hz, class B, 2
speeds.
o CAB-PLUS 250: IP20 single-phase asynchron motor 230V, 50 Hz, class B, 2 speeds.
o CAB-PLUS 315: IP55 single-phase asynchron motor 230V, 50 Hz, class F, 2 speeds.
o Motors with incorporated thermal protection with non-automatic resetting.
3. INSTALLATION
3.1 Dimensions and weights
E
B
C
Sizes
CAB-PLUS 125
CAB-PLUS 160
CAB-PLUS 250
CAB-PLUS 315
Dimensions in mm
3.2 Installation
The cabinet fan must be fixed on a plan support by the holes foreseen. Installation on anti-vibration mounts
and connection with flexible sleeves are recommended.
Access to the filter and to the motor fan is possible thanks to the cover: to be foreseen enough room, at least
C dimension of the cabinet for servicing and maintenance operations.
The aeraulics installation of the cabinet and its ventilation duct must achievement must satisfy to the technical
conditions defined on DTU 68-2.
If the cabinet fan is installed in or close to a place equipped with a boiler or another type of combustion device,
appropriate precautions shall be taken to avoid any gas o smoke exhaust coming from evacuation pipe of gas
device (boilers, ...) or any fire devices (chimney, stove, ...) inside the room.
G H
Cabinet fan
A
B
C
ØD
340
330
210
125
406
468
235
160
490
488
364
250
537
544
380
315
F
J
A
Fixations
E
F
G
H
93
415
364
350
129
490
502
482
178
630
530
514
194
652
587
565
10
Weights
J
(kg)
250
7
360
13
400
20
470
24