Control Voltage Wiring; 7Th Step - Perform The Adjustments Of The Factory-Installed Options - Carrier 50TCN120 Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Picture 9 – High Voltage and Control Connection
CONTROL VOLTAGE WIRING – NOTE: Do not use
any kind of thermostat that absorbs power. It can
cause control problems to the unit.
NOTE: For cables up to 15 m, use an insulating
cable (35°C minimum) No. 18 AWG (American
Wire Gauge). For 15 to 23 m, use an insulating
cable (35°C minimum) No. 16 AWG (American Wire
Gauge). For more than 23 m, use an insulating
cable (35°C minimum) No. 14 AWG (American Wire
Gauge). All the cables longer then No, 18 AWG
cannot be directly connected to the thermostat
and require a joint box to be connected to the
thermostat. See the Table for the American /
European cable conversions.
1. If the unit is assembled on a Roof Curb and
a connection to the service plate is used
through the curb, direct the cables through the
connection plate.
2. Connect the thermostat cables to the screw
terminals of the low voltage connector.
Picture 10 – Location of the access panel
American and European Wiring Conventions
7th Step – Perform the Adjustments of the
Factory-Installed Options
MANUAL OUTSIDE AIR LOUVER
1. Determine the amount of ventilation air
required for the building.
2. Remove the access panel to the fi lter, raising
and turning the panel to the outside. The
panel is now unhooked from the rail and can
be removed. Remove and sep the outside air
opening panel and the screws. See Picture 11.
Picture 11
3. Detach the cover and the base panel removing
the screws and the brackets hold by them. Keep
all the screws and dispose the brackets.
41