steel fixing flange for model BT - 100 - 120 DSNM-D
1 - Boiler plate
2 - Insulating gasket
3 - Burner fixing flange
4 - Elastic collar
or model BT 75-180-250 -300 - 350 DSNM-D
f
When tightening the flange, it is important to do it evenly so that the inner faces are parallel between them. Since the locking
!
system is highly efficient, do not tighten the nuts too much. During this operation (tightening of the flange locking nuts) keep the
body of the burner lifted so that the combustion head is kept in a horizontal position.
The burner is correctly installed when the pre-heating tank is slightly inclined (higher on the side where fuel exits to go to the
!
nozzle). This inclination serves to prevent gas from building up inside the tank.
Presence of gas in the pre-heating tank will greatly increase the time required to pressurise the fuel, and it is quite likely that the
burner will go into "block". Be careful when installing the burner on the boiler that the burner is not positioned where it cancels this
inclination or, even worse, where the pre-heating tank is sloping in the opposite direction to the direction desired.
5 - Stud bolt
6 - Locking nut with washer
7 - Nut and washer for fastening the first
flange
1 - Boiler plate
2 - Insulating gasket
3 - Burner fixing flange
4 - Stud bolt
5 - Locking nut with washer