baltur BT 75 DSNM/D Manual De Instrucciones página 16

Quemador de petroleo pesado a dos etapa
Ocultar thumbs Ver también para BT 75 DSNM/D:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DIAGRAM OF A DISMANTLED (CB) CHARLES BERGONZO NOZZLE(WITHOUT PIN)
E
Nozzle ID:
N
Flow rate in kg/h
Spray angle (30° - 45° - 60° - 80°)
G
Flow ratio (1/3 =B3 - 1/5 = B5)
L
I
S
H
Fuel outlet
N.B. For the nozzle to operate properly, its "return" section must never be completely closed.
This is achievedby regulating when the burner is started up for the first time. In practice, when the nozzle is operating at the maximum flow rate,
the difference in pressure between the "delivery" (pump pressure) and "return" (pressure at hte returnpressure regulator) pressures (running to
and from the nozzle) must be at least 2÷3 bar.
Example:
Pump pressure
Return pressure
BALTUR PUMP MODEL BT.....
Pump pressure regula-
tion (20 ÷ 22 bar)
Air turbulence chamber
20 bar
20 - 2 = 18
20 - 3 = 17
Suction
Pump pressure regula-
tion (20 ÷ 22 bar)
Suction
Pump plate
0006080092_201011
Viton O-ring
(oil and temperature reristant)
Fuel inlet
Fuel return holes
Pump pressure
22 bar
Return pressure
22 - 3 = 19 bar
22 - 2 = 20 bar
1/4" Vacuum-meter connection
Return
Pump plate
1/4" Pressure gauge connection
Heating element seal
1/4" Vacuum-meter connection
Return
1/4" Pressure gauge connection
Heating element seal
14 / 30
Fuel return
Delivery (nozzle)
Delivery (nozzle)