baltur BT 75 DSNM/D Manual De Instrucciones página 12

Quemador de petroleo pesado a dos etapa
Ocultar thumbs Ver también para BT 75 DSNM/D:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

BASIC HYDRAULIC DIAGRAM FOR MULTIPLE TWO-FLAME OR MODULATING BURNERS USING FUEL
E
OIL (MAX 15 °E AT 50 °C)
N
G
L
I
S
H
N.B. The thank for recovery of hot oil (diameter 150 mm, height 400
mm) should be installed as near as possible to the burner and
about 0.5 m, above the pump.
BASIC HYDRAULIC DIAGRAM FOR MULTIPLE TWO-FLAME OR MODULATING BURNERS USING FUEL
OIL (MAX 15 °E AT 50 °C)
1
- MAIN TANK
2
- FILTER
3
- CIRCULATION PUMP
4
- WATER AND SYSTEM DISCHARGE
5
- NORMALLY CLOSED AIR-GAS
DISCHARGE
6
- FUEL RECOVERY TANK AND
DEGASSING UNIT
7
- NON-RETURN VALVE
6
- BY PASS (NORMALLY CLOSED)
9
- ADJUSTABLE PRESSURE REGULATOR,
0.5 - 2 BAR
10 - PRESSURE GAUGE (0-4 BAR)
11 - HEAVY OIL HEATING COIL, STEAM
OR HOT WATER
HEATING ELECTRICAL LEAD
(IF NECESSARY)
N.B. The thank for recovery of hot oil (diameter 150 mm, height 400 mm) should be installed as near as possible to the burner and about
0.5 m, above the pump.
1
- MAIN TANK
2
- FILTER
3
- CIRCULATION PUMP
4
- WATER AND SYSTEM DISCHARGE
5
- NORMALLY CLOSED AIR-GAS DISCHARGE
6
- FUEL RECOVERY TANK AND DEGASSING UNIT
7
- NON-RETURN VALVE
6
- BY PASS (NORMALLY CLOSED)
9
- ADJUSTABLE PRESSURE REGULATOR, 0.5 - 2 BAR
10
- PRESSURE GAUGE (0-4 BAR)
10 / 30
0006080092_201011

Publicidad

Tabla de contenido
loading

Tabla de contenido