Typical application
Fig. 1-2;
If the appliance is installed at a height of less than 2.3
metres from ground level and the length of the
ducting connected to the inlet and outlet so requires,
special safety devices should be fitted to prevent any
risk of contact with the blades.

Installation

Fig. 3 ÷14;
Fig.3: B= Air flow direction data plate; C= Air Inlet; D=
Air Outlet;

Function

Figs. 15÷22.
The appliance leaves the factory with Minimum (V min )
and Maximum (V max ) speeds set at their nominal
values.
The electronic board fitted to the appliance has two
potentiometers for setting V min and V max (fig.15).
Pre-set speed changes (set by installer)
Any initial adjustment of V min and V max can be
carried out as follows:
- Turn the potentiometers fully anti-clockwise before
connecting the appliance to the mains (fig. 16);
- turn the appliance ON;
- within one hour of turning the appliance ON,
proceed as follows:
* position the external switch at V min ;
* use the V min potentiometer to set V min at the
desired speed; (fig .19)
* position the external switch at V max;
* use the V max potentiometer to set V max at the
desired speed (fig. 20).
* wait about 10 minutes before turning the
appliance off to allow the system time to memorise
the speeds that have been set.
NOTE:
Only adjust the trimmer using non-conductive tools
(e.g. a plastic screwdriver). Any subsequent
adjustments can be made using the same sequence
as above.
Restoring the original speed settings (set by
installer) (Mod.100 ÷ 200)
- With the appliance turned off, change the original
settings of the dip-switches shown in fig 22. The
new setting will only be temporary and can be any
of those shown in the table for this appliance. (table
A or B)
- Fully turn the Max and Min speed adjuster anti-
clockwise.
- Turn the appliance on and let it run for at least 10
minutes.
- Turn the appliance off and restore the original dip-
switch settings (table A or B).
- Turn the Minimum and Maximum speed adjusters
clockwise to the half-way stage.
- Turn the appliance on again.
TAB A
Model
LINEO 100Q ES
LINEO 100 ES
LINEO 125 ES
TAB B
Model
LINEO 150 ES
LINEO 160 ES
LINEO 200 ES
Configuration
ON
OFF
1
2
3
4
ON
OFF
1
2 3
4
ON
OFF
1
2
3
4
Configuration
ON
OFF
1
2
3
4
ON
OFF
1
2
3
4
ON
OFF
1
2
3
4