Ecoflam BLU 1500.1 LN PRE Serie Manual De Uso página 12

Ocultar thumbs Ver también para BLU 1500.1 LN PRE Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 36
EN
Start up
- Adjusting burner output
Adjusting the maximum air flow rate
Air and Gas adjustment are accomplished
through BT3XX parameters setting. Refer
to BT3XX manual attached.
Adjusting the minimum capacity of the
burner
Air and Gas adjustment are accomplished
through BT3XX parameters setting. Refer
to BT3XX manual attached.
Adjusting the intermediate capacity of
the burner
Gas adjustment is accomplished through
BT3XX parameters setting. Refer to
BT3XX manual attached.
N.B. observe the minimum required
flue gas temperature specified by the
boiler manufacturer and the requirements
demanded of flue gas ducts for avoiding
condensation.
!
Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of the burner. Optimise combustion values in the
event of CO formation. CO must not exceed 50 ppm.
12
www.ecoflam-burners.com
Firing head setting (C).
The firing head position adjustment is made
in order to obtain the best combustion effi-
ciency. When used with minimum outputs
the firing head is adjusted in rear position.
With high output, the firing head is adjusted
in forward position. Adjustment:
• loosen screw V through a suitable Allen
key.
• by a screwdriver act on the hex. head
screw U until is reached the desired posi-
tion.
• tighten screw V.
Adjustment of gas solenoid valve
Refer to the gas train manual for the gas
setting of the gas train selected.
C
+
U
B
420010721500
V
A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Blu 1700.1 ln pre serieBlu 2000.1 ln pre serieBlu 1500.1 ln pre tcBlu 1500.1 ln pre tlBlu 1700.1 ln pre tcBlu 1700.1 ln pre tl ... Mostrar todo

Tabla de contenido