Restoring nominal values

If necessary, the nominal factory-set values for V1
and V2 can be restored using the following
procedure:
- cut off the power supply
- set the dip-switch SW2 indicated
in the figure:
Int.3=ON
- restore the power supply:
V1 and V2 are automatically restored to the nominal
factory-set values corresponding to the selected
model, as described above. The restoring of
nominal values is indicated by two quick flashes of
an LED on the card.
The motor is deactivated automatically
- cut off the power supply
- reset
the
dip-switch
indicated in the figure:
Int.3=OFF

Operation

Depending on the mode selected during installation:
- two-speed
mode:
continuously; two speeds V1 and V2 can be
selected using an external switch
- adjustable speed mode: the appliance can operate
at a speed which is adjusted between 300 Rpm and
Vmax (via an external potentiometer). The Vortice
ON/OFF control box + potentiometer (code 12826,
on request) can also be used.

Maintenance / Cleaning

Fig. 27, 28, 29.