9-9-1. Calculation of the amount of additional refrigerant
・The amount of refrigerant to be added depends on the size and the total length of the liquid piping.
・Calculate the amount of refrigerant to be charged according to the formula below.
・Round up the calculation result to the nearest 0.1 kg (0.1 oz).
(1) Units "m" and "kg"
<Formula>
・When the piping length from the outdoor unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
ø19.05 total length
additional
=
× 0.29 (kg/m)
charge (kg)
Outdoor unit
model
(E)P72
(E)P96
(E)P120
(E)P144
+
(E)P168
EP192
EP216
EP240
* Amount of refrigerant to be
charged for single-module units
・When the piping length from the outdoor unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
ø19.05 total length
additional
=
× 0.26 (kg/m)
charge (kg)
Outdoor unit
model
(E)P72
(E)P96
(E)P120
(E)P144
+
(E)P168
EP192
EP216
EP240
* Amount of refrigerant to be
charged for single-module units
* When connecting PLFY-EP06NEMU-E, add 0.4 kg of refrigerant per indoor unit.
* When connecting PLFY-EP18NEMU-E1, add 0.4 kg of refrigerant per indoor unit.
* When connecting PLFY-EP30NEMU-E, add 0.4 kg of refrigerant per indoor unit.
* When connecting PLFY-EP36NEMU-E, add 0.4 kg of refrigerant per indoor unit.
* When connecting PEFY-P06NMAU-E, add 0.3 kg of refrigerant per indoor unit.
* When connecting PEFY-P24NMAU-E, add 0.3 kg of refrigerant per indoor unit.
* When connecting PEFY-P36NMAU-E, add 0.3 kg of refrigerant per indoor unit.
<Example>
Outdoor unit model: P120
Total capacity of connected indoor units: 144
* Refer to the pipe connection examples in section 9-4 for the pipes marked with the letters below.
A : ø12.7; 40 m
B : ø9.52; 10 m
C : ø9.52; 15 m
D : ø9.52; 10 m
a : ø9.52; 10 m
b : ø9.52; 5 m
c : ø6.35; 10 m
WT09452X01
ø15.88 total length
ø12.7 total length
+
+
× 0.2 (kg/m)
× 0.12 (kg/m)
Total capacity of connected
Amount (kg)
indoor units
0
27 or below
0
0
55 to 126
0
127 to 144
0
145 to 180
+
0
181 to 234
4.4
235 to 273
4.4
274 to 307
308 to 342
343 to 411
412 to 480
481 or above
ø15.88 total length
ø12.7 total length
+
+
× 0.18 (kg/m)
× 0.11 (kg/m)
Total capacity of connected
Amount (kg)
indoor units
0
27 or below
0
0
55 to 126
0
127 to 144
0
145 to 180
+
0
181 to 234
4.4
235 to 273
4.4
274 to 307
308 to 342
343 to 411
412 to 480
481 or above
GB-39
ø9.52 total length
+
× 0.06 (kg/m)
Amount (kg)
2.0
28 to 54
2.5
3.0
3.5
4.5
5.0
6.0
8.0
9.0
10.0
12.0
14.0
ø9.52 total length
+
× 0.054 (kg/m)
Amount (kg)
2.0
28 to 54
2.5
3.0
3.5
4.5
5.0
6.0
8.0
9.0
10.0
12.0
14.0
ø6.35 total length
+
× 0.024 (kg/m)
ø6.35 total length
+
× 0.021 (kg/m)