Electrical Connection - Rechner Sensors i-LeVeL Instrucciones De Servicio

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Mounting
It is mandatory to have a galvanic connection between the sensor head and an earthed container (or ad-
ditional electrode)! With metal containers the BE-connection is normally made through the threading of the
sensor to the metal container. With non-metal containers the connection to the BE electrode is made by
means of a cable via an M3 threaded hole at the rear of the sensor.
D
≥15 mm
Measuring range (M) non-active range (IB1) non-active range (IB2)
Do not mount the measuring range in the area of the container with changes in the cross sec-
tion, like the bottom cone of the container
The probe can be mounted in the centre of the container or just off to one side. For a measurement to be independent of the filling
cone, we recommend that the probe be mounted at ¼ of the diameter. The minimum distance between the end of the measuring range
and the container's lid is 50 mm.

Electrical Connection

¼D
1/3D,
IB1
min. 50 mm
M
IB2
Electrical connection:
• Disconnect the system from all power
• Connect the probe according to the connection diagram
• Switch power on
• The sensor automatically detects during starting for each
switching output individually, if the switching output is con-
nected to a "-" (=PNP) or "+" (=NPN) load.
Load resistor is ≤ 20 k Ohm for the digital outputs S MIN
and S MAX.
2
1
5
3
4
KFI-1-...
Connect the BE through the pro-
cess connection or by means of
the rear screw connection.
Pin connection
Pin 1: +24 V
Pin 2: SWITCH MAX
Pin 3: GND
Pin 4: SWITCH MIN
Pin 5: ANALOGUE OUT
BE
13