Hitecsa EWMIG 236 Manual De Instalación, Uso Y Mantenimiento página 125

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

EWMIG model
Application with fan coil
Cooling capacity MIN/NOM/MAX (1)
ESEER +
Nominal cooling capacity (1) (*) EN 14511:2013
EER EN 14511:2013 (1) (*)
ESEER EN 14511:2013
Heating capacity MIN/NOM/MAX (2)
Nominal heating capacity (2) (*) EN 14511:2013
COP EN 14511:2013 (2) (*)
Application radiant
Cooling capacity MIN/NOM/MAX (3)
Nominal cooling capacity (3) (*) EN 14511:2013
EER EN 14511:2013 (3)
Heating capacity MIN/NOM/MAX (4)
Nominal heating capacity (4) (*) EN 14511:2013
COP EN 14511:2013 (4) (*)
Energy class (§)
Sound pressure (5) (O)
Sound power (6) (O)
Scroll compressor
Fans
Heat exchanger water content
Heat exchanger nominal flow water side (1)
Water side heat exchanger nominal pressure drops (1)
Water side heat exchanger nominal pressure drops (2)
Residual head (P1/PI1 mounting) (1)
Residual head (P2/PI2 mounting) (1)
Residual head (ASP1/ASPI1 mounting) (1)
Residual head (ASP2/ASPI2 mounting) (1)
Nominal heating capacity RC100 (±)
Nominal flow rate/pressure drop RC100 (±)
Nominal heating capacity DS (±)
Nominal flow rate/pressure drop DS (±)
Tank water content
Amount of R410A refrigerant
Type / Amount of Oil
Electrical data
Absorbed power in summer mode NOM (1) (●)
Absorbed power in winter mode NOM (2) (●)
Absorbed power in summer mode NOM (3) (●)
Absorbed power in winter mode NOM (4) (●)
Pump absorbed power (P1/ASP1) / (PI1/ASPI1)
Pump absorbed power (P2/ASP2) / (PI2/ASPI2)
Electrical power supply
Auxiliary power supply
Nominal current (■)
Maximum current (■)
Starting current (■) (7)
Pump absorbed current (P1/ASP1) / (PI1/ASPI1)
Pump absorbed current (P2/ASP2) / (PI2/ASPI2)
Dimensions
Width
Height
Depth
Water connections
(1) In the following conditions: Condenser inlet air temperature 35°C; chilled water
temperature 7°C; temperature differential at evaporator 5°C.
(2) In the following conditions: Evaporator inlet water temperature 7°C B.S., 6°C
B.U.; hot water temperature 45°C; temperature differential at evaporator 5°C.
(3) In the following conditions: Condenser inlet air temperature 35°C; chilled water
temperature 18°C; temperature differential at evaporator 5°C.
(5) Sound pressure level in dB(A), referring to a 5 m distance from the unit, with
directionality factor = 2.
(6) Sound power level in dB(A) on the basis of measurements taken in
accordance with UNI EN-ISO 9614 and Eurovent 8/1 Standards.
(7) The value of the inrush current is valid upon the activation of the second
compressor (FixSpeedCompressor).
(±) Recovery unit heating capacity Conditions referring to the unit operating with
chilled water temperature 7°C, differential temperature due to evaporation of 5 K,
ALLEGATI / ENCLOSED DOCUMENTS / ANNEXOS / ANLAGEN / ANEXOS
236
kW
11/34,5/35,4
14,8/46,1/47,3
5,07
kW
11/34,3/35,2
14,7/45,7/46,9
2,60
4,61
kW
8,8/39,6/40,9
10,4/50,1/51,8
kW
8,9/39,9/41,2
10,4/50,5/52,3
3,22
kW
13,7/41,5/43,1
18,5/55,9/58,1
kW
13,6/41,2/42,8
18,4/55,4/57,5
3,27
kW
9,7/38,5/40,2
kW
9,7/38,8/40,5
3,78
A++
dB(A)
54
dB(A)
78
n° x kW
1x 0,61
l
3,8
l/h
5900
kPa
31
kPa
39,7
kPa
129
kPa
212
kPa
126
kPa
210
kW
40,1
1,3 / 12
m³/h/kPa
kW
14,6
m³/h/kPa
6,9 / 45
l
80
kg
9,17
l
PVE (FV68S)/ 3.4 PVE (FV68S)/ 3.4 PVE (FV68S)/ 3.4 POE (160SZ) / 6.6
236
kW
4,1/13,2/13,3
kW
2/12,1/12,6
kW
4,4/12,3/12,3
kW
2/10/10,5
kW
1,04
kW
1,73
V-ph-Hz
V-ph-Hz
A
26,4
A
32,3
A
80
A
1,86
A
3,15
236
mm
1660
mm
1570
mm
1000
2"
Ø
hot water temperature produced equivalent to 40/45°C (RC100) 50/60°C (DS).
NB. With heat pumps operating in winter mode with DC active, the heating
capacity available is decreased from the portion supplied to the desuperheater.
(■) Current absorbed by compressors and fans.
(●) Power absorbed by compressors and fans.
(*) The data according to EN 14511 refer to the Standard set up. Refer to the
section "Technical Note Attachments" for information relating to the Pump and
Tank&Pump set up.
(O) With the SIL accessory, the value decreases by 3dB(A).
ESEER (European Sesonal EER) European average seasonal ef- ficiency.
ESEER+ with AdaptiveFunction Plus logic
(§) A low temperature according to the Regulation n ° 811/2013
127
245
250
16,1/50,3/51,6
4,69
5,00
16/50/51,3
3,04
3,01
4,19
4,23
13/56,1/57,8
13/56,5/58,2
3,30
3,23
20/60,9/63,3
20/60,4/62,8
3,58
3,72
12/50,2/52,5
13,9/53,7/56
12/50,6/53
13,9/54,1/56,4
3,85
3,90
A++
A++
56
56
80
80
Scroll regulated by inverter
2 x 0,61
2 x 0,61
3,8
4,4
7900
8600
52,5
35,3
61
43,4
101
114
182
196
96
109
178
190
54
63
1,7 / 12
1,8 / 16
19,4
20,6
9,3 / 46
10,8 / 49
150
150
11,3
18,5
245
250
5,1/15,1/15,2
5,5/16,6/16,8
2,7/14,9/15,6
3,4/17,1/17,8
5,5/14,9/15
5,9/15,8/15,9
2,8/12,7/13,4
3,1/13,5/14,2
1,04
1,04
1,73
1,73
Water outlet
230-1-50
32,2
36,1
41
42,4
78
82
1,86
1,86
3,15
3,15
245
250
2660
2660
1570
1570
1000
1000
2"
2"
260
18,2/58,6/60,2
4,93
18,2/58,3/59,9
2,75
4,48
14,1/68,5/70,9
14,1/68,9/71,3
3,20
24,3/75,5/78,6
24,3/75/78
3,67
16,2/68,9/72,1
16,3/69,3/72,6
3,84
A++
57
81
2 x 0,61
5,1
10100
29,9
39,5
111
193
104
186
69,8
2,1 / 16
24,2
12 / 46
150
19,83
260
6,8/21,2/21,4
3,6/21,1/22
7,3/19,9/19,9
3,6/17,6/18,5
1,04
1,73
45,4
54,5
147
1,86
3,15
260
2660
1570
1000
2"

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ewmig 245Ewmig 260

Tabla de contenido