– Position the lower front wall (11) by
fitting it in between the screws on
t he bur ner manif old suppor t
brackets and the cast iron body;
anchor the walls to panels (6) and
(9) with two 7SP x 1/2" self-tapping
screws.
– Position the upper front wall (12) by
anchoring it to panels (5-8) and to
wall (11) using four 7SP x 1/2" self-
tapping screws.
– Anchor the rear wall (13) to panels
(4-5) and (7-8) using the eight 7SP x
1/2" self-tapping screws supplied.
– Assemble the baseboard (14),
anchoring it to panels (6) and (9)
using connecting pins.
– Proceed in the same way to anchor
the upper front panel (16) in place.
– Assemble the cover (10) and the
door (15).
2. 1 2
ASSEMBLING THE GAS
ASSEMBLY
Connect the gas assembly to the bur-
ner manifold as shown in fig. 12. The
gas assembly may be assembled on
the right or left side of the manifold.
WARNING: in case of the gas assem-
bly is mounted on the left side of the
manifold, remove and rotate the gas
valve of 180° to get access frontally
at the regulations.
2. 1 3
ASSEMBLING THE CONTROL
PANEL (fig. 12/a)
Remove the control panel's protective
cover and insert the wiring guard on
the front upper panel, anchoring it in
place with the screws provided. Repla-
ce the cover. Proceed to assemble the
instrument panel, anchoring it in place
with the screws provided. Insert the
instrument bulbs in their sheaths: first
insert the control thermostat bulb,
pushing it in until it touches the bot-
tom of the sheath.
WARNING: To ensure correct tem-
perature control in the boiler, the
bulbs of the control and safety devi-
ces must be inserted in the sheath
from the side corresponding to the
heating system delivery and return
connections. If the heating system
delivery and return connections are
on the left side of the generator, the
gas assembly must also be assem-
bled on the left side to permit this
arrangement.
64
KEY
1 Burner manifold
2 Gas assembly
3 Bulb sheath
2. 1 4
ASSEMBLING THE
ELECTRICAL PANEL
(fig. 12/b)
Remove the cover of the electrical
panel and anchor the control panel to
the lower front wall using the screws
provided. Connect the two sockets to
the plugs from the control panel. Com-
plete the electrical panel by hooking up
the gas valve, the second gas solenoid
valve, the gas pressure switch and the
KEY
1 Protective cover
2 Wiring guard
3 Front upper panel
4 Instrument panel
5 Instrument bulbs
6 Sheath
7 5 pole plug
8 7 pole plug
KEY
1 Cover
2 Electrical panel
3 Lower front panel
4 5 pole plug
5 7 pole plug
6 Second gas solenoid valve cable
7 Gas pressure switch cable
8 Gas valve cable
9 Coil cable
10 Detection electrode
11 Ignition electrode
coil. Unwind the cables of the ignition
and detection electrodes emerging
from the electrical panel. Insert the
ignition electrode in the hole between
the head and the intermediate on the
gas assembly side, anchoring it to the
two stud bolts (fig. 12/c).
Perform the same operation on the
detection electrode, which will go in
the hole provided between the head
and the intermediary at the other end
of the body.
3