Servicing Instructions - Leviton 57000 Serie Instrucciones De Instalación

Ocultar thumbs Ver también para 57000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

• A 7/8 inch hole cut on the hinged side of the enclosure is recommended
for the Remote Supervisor Panel connections. See Remote Supervisor
Panel instructions for its connection method.
9. Battery Installation: A 9-Volt alkaline battery is included in the shipping
carton. The purpose of the 9-Volt battery is to power the diagnostic warning
circuitry in the event of a power failure or multiple fuse failures. Remove the
battery holder from the diagnostic assembly. Insert the 9-Volt battery (be
sure to follow the polarity markings on the battery compartment), and slide
the battery holder back in.
10. Secure modules and replace terminal block cover. Be certain all TVSS
Modules are tightly in place and remove any extra materials. Close and
secure enclosure cover door before applying power.
11.
Activate the system by turning AC power ON: The 6 Green
Module Status lights should be illuminated and visible through the ports
in the enclosure door, and all other lights should be OFF. If problems
are encountered that can not be resolved using the Problem Isolation
Procedure printed on the inside of the enclosure door, contact Leviton
Technical Support: 1-800-648-3332.
12. Diagnostic Test: Press and hold down the test button. The Red warning
indicator should blink, the audible tone signal should beep, the Yellow low
battery light should illuminate, and the Remote Supervisor Panel warning
indicator, if wired in, will be activated. Release the test button.
13. Surge Counter Test: If the 57000 Panel has a LCD surge counter on it's
front panel, press it's "Reset" switch, then the "Test" switch. The display
should register surge counts each time the "Test" switch is depressed.
The "Reset" switch should be depressed whenever the LCD display is at
a maximum (the LCD unit's red LED will be illuminated). "Reset" may be
depressed anytime to clear the display.
Leviton Series 57000 TVSS Servicing Instruction Procedure: Carefully
read these instructions as well as the Module and Fuse Replacement
Instruction Procedure before attempting service.
CAUTION:
BEFORE OPENING TVSS ENCLOSURE COVER, POWER
MUST BE TURNED OFF. ELECTROCUTION AND FATAL OR SERIOUS
INJURY AND PROPERTY DAMAGE CAN RESULT FROM FAULTY
SERVICING. IT IS RECOMMENDED THAT THE 57000 TVSS PANEL
PROTECTION SYSTEM BE SERVICED BY A QUALIFIED ELECTRICIAN.

SERVICING INSTRUCTIONS

Page 8

Publicidad

Tabla de contenido
loading

Tabla de contenido