Alliance Laundry Systems AT120FG Manual Del Usuario página 45

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

120 Pound Tumblers
8
7
6
NOTE: Sizing of pipe diameters is shown for steam at rated pressure of 120 psi. Pipe diameter needs to be increased
accordingly if pressure is less than 125 psi (refer to Table 8). Piping must also be sized accordingly for length of runs
and number of elbows.
1
Risers 12 in. (305 mm)
2
Shut-Off Valve
3
Check Valve
4
Condensate Return Line from Supply Line
5
Vacuum Breaker
Model
120CSH
120CSH
120CSH
M414038
SUPPLY
2
5
4
3
Steam Pressure
(psi)
120 – 125
60 – 120
35 – 60
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
1
9
3
10
5
6
18 in. Drop (457 mm)
7
Solenoid Valve (Supplied with machine)
8
Steam Bonnet
9
Union
10
Trap with Built-In Strainer
Figure 16
Minimum Pipe Diameter
1 in. (25 mm)
1 in. (25 mm)
1.25 in. (32 mm)
Table 8
Steam Requirements
2
RETURN
T221I
Steam Trap Size
(Pounds Condensate/Hour)
345
345
345
T221I
43

Publicidad

Tabla de contenido
loading