Wireless Remote Controller - Mitsubishi Electric Mr.Slim SLZ-KA25 Para El Instalador

Ocultar thumbs Ver también para Mr.Slim SLZ-KA25:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 62
10.Test run
h
ON/OFF
TOO
TOO
WARM
COOL
The OPERATION INDICATOR
lamp comes on regardless of
the remote controller display.
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp flash
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
Number of flashes/beeps in pattern indicates the check
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp flash
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
[Output pattern A] Errors detected by indoor unit
Beeper sounds/OPERATION
INDICATOR lamp flashes
1 Check code
(Number of times)
1
P1
2
P2, P9
3
E6, E7
4
P4
5
P5
6
P6
7
EE
8
P8
9
E4
10
11
12
Fb
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Beeper sounds/OPERATION
INDICATOR lamp flashes
1 Check code
(Number of times)
1
E9
2
UP
3
U3, U4
4
UF
5
U2
6
U1, Ud
7
U5
8
U8
9
U6
10
U7
11
U9, UH
12
13
14
Others
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2 If the beeper sounds three times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial two beeps to confirm the self-check start signal was received, the
specified refrigerant address is incorrect.
14
OPERATION INDICATOR lamp
Beep
Beep
Beep
Beep
1
st
2
nd
3
rd
n
th
On
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Beep
Beep
st
nd
1
2
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "P5")
Intake sensor error
Pipe (Liquid or 2-phase pipe) sensor error
Indoor/outdoor unit communication error
Drain sensor error
Drain pump error
Freezing/Overheating safeguard operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
Indoor unit control system error (memory error, etc.)
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating safeguard operation
Abnormal temperature of heat sink
Outdoor unit fan safeguard stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal synchronous
signal to main circuit/Current sensor error
Other errors (Refer to the technical manual for the outdoor unit.)

10.4.2. Wireless remote controller

1 Turn ON the power.
2 While pressing both the MODE SELECT button and TOO COOL button on the
remote controller at the same time, press the RESET button.
3 Release the RESET button.
4 Release the other two buttons. After three seconds, all items in the LCD are dis-
played.
5 Transmit the signal of remote controller by pressing the OPERATE/STOP (ON/
OFF) button on the remote controller.
(The above procedure allows OPERATION INDICATOR lamp to indicate the fail-
ure-mode.)
6 Transmit the signal of remote controller by pressing the OPERATE/STOP (ON/
OFF) button to stop the self-check.
Beep
Beep
1
st
2
nd
· · · Repeated
Off
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
Beep
Beep
rd
th
3
n
On
On
Off
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
Symptom
Symptom
Beep
Beep
st
nd
1
2
· · · Repeated
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
Remark
Remark
For details, check the LED display
of the outdoor controller board.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mr.slim ka35Mr.slim ka50vaMr.slim ka25Mr.slim ka50val

Tabla de contenido