10.11 Device safety
Design to:
EN 61010 Part 1
Protection Class:
Protection Class 2 (front side)
Only the front side is classified as accessible
for the operator.
Application area:
Insulation:
Signal inputs and und sensor power supply: SELV
10.12 Mechanical Data
Housing:
Panel-mount housing
to DIN 43 700, RAL 7021
Dimensions:
48 x 48 x 91 mm
Panel cut-out:
45
Installation depth:
ca. 107 mm incl. terminals
Weight:
ca. 125 g
Protection:
IP65 (front, device only)
Housing material:
Polycarbonate UL94 V-2
Vibration resistance: 10 - 55 Hz / 1 mm / XYZ
(EN60068-2-6):
30 min in each direction
Shock resistance
100G / XYZ
(EN60068-2-27):
3 times in each direction
(EN60068-2-29):
10G/6 ms/XYZ 2000 times in
each direction
10.13 Connections
Supply voltage and outputs:
Plug-in screw terminal, 7-pin, RM5.08
Core cross section, max. 2.5 mm²
Signal and control inputs:
Plug-in screw terminal, 8-pin, RM 3.81
Core cross-section, max. 1.5 mm²
11 Scope of Delivery
Delivery includes:
Preset counter
Mounting clip
Instruction manual
Page 20
Pollution level 2
over-voltage Category II
Front: double insulation,
Rear side: basic insulation,
+0,6
+0,6
x 45
mm
12 Ordering codes
6.924.X1XX.XX0
Input trigger levels
Supply voltage
LCD version
Outputs
Front
* 24 VAC power supply on request
13 Frequencies (typical)
13.1
Pulse counter
HTL level
AC supply
DC supply 12V
DC supply 24V
Add
Sub
Trail
55 kHz
Cnt.Dir
Up.Dn
29 kHz
Up.Up
Quad
28 kHz
Quad 2
18 kHz
Quad 4
A/B
(A-B)/A
0 = Standard (HTL)
A = 4-30 VDC*
0 = 100... 240 V AC ± 10%
2 = 24 VAC +/- 10%
3 = 10 .. 30 VDC
0 = no backlighting
1 = green backlighting*
2 = LED Look*
3 = Multicolour
0 = Relay
1 = Optocoupler*
0 = Kübler version
A = Neutral version*
typ. Low
2,5 V
typ. High
22 V
typ. Low
2 V
typ. High
10 V
typ. Low
2,5 V
typ. High
22 V
AddAr
AddTot
SubAr
SubTot
AddBat
SubBat
TrailAr
2,8 kHz
2,7 kHz
2,8 kHz
2,7 kHz
1,4 kHz
1,3 kHz
1,2 kHz
0,9 kHz
29 kHz