Wiring the device modules
Communication modules
DIP switch
Pos.
Description
Addressing of the bus node
A
O
N
d
Fig.6-3
For the DIP switches that are placed at the front
the node address (labelling "1" ... "64") and
ƒ
baud rate (labelling "a" ... "d")
ƒ
can be set.
Note!
If all address switches adopt the "OFF" position when the basic device is
switched on, the configurations of codes C00350 (nodes address) and C00351
(baud rate) apply.
Switch the voltage supply of the basic device off and then on again to activate
altered settings.
Setting the node address
The node address of the drive is calculated from the sum of all address switches in the "ON"
position.
Setting the baud rate
d
c
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
Displays
Pos.
Colour
MS
Green
DE
Red
BS
Green
BE
Red
104
c
b
a
64
32
16
8
4
2
1
Baud
CAN Address
Arrangement and labelling of the DIP switches
b
a
Baud rate
ON
OFF
10 kbit/s
OFF
ON
20 kbit/s
ON
ON
50 kbit/s
ON
OFF
125 kBit/s
OFF
ON
250 kbit/s
OFF
OFF
500 kbit/s
ON
OFF
800 kbit/s
OFF
OFF
1000 kbit/s
ON
ON
Auto baud
Condition
On
On
Signalling according
to DR303-3
Description
Communication module is supplied with voltage.
Communication module is not accepted by the standard device
(see notes given in the documentation for the standard device).
CANopen state ("Z")
CANopen error ("F")
9400CAN003
EDK94SH366 DE/EN/FR/ES/IT 3.1