Lenze E94ASHE Serie Instrucciones Para El Montaje página 77

Ocultar thumbs Ver también para E94ASHE Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Rated values for internal brake chopper
Operation at a rated mains voltage of 400 V
Type
E94ASxE1454
E94ASxE1724
E94ASxE2024
E94ASxE2454
E94ASxE2924
E94ASxE3664
E94ASxE4604
E94ASxE5724
E94ASxE6354
E94ASxE6954
Operation at a rated mains voltage of 500 V
Type
E94ASxE1454
E94ASxE1724
E94ASxE2024
E94ASxE2454
E94ASxE2924
E94ASxE3664
E94ASxE4604
E94ASxE5724
E94ASxE6354
E94ASxE6954
EDK94SH366 DE/EN/FR/ES/IT 3.1
Switching
Minimum
threshold
brake resistor
(adjustable)
U
[V]
R
[Ω]
BRmax
Bmin
725
5.0
725
4.3
725
3.5
725
2.8
725
2.3
725
1.8
725
1.4
725
1.2
725
1.1
725
1.1
I
, P
Periodic load change of 0.5 s and recovery time of 4.5 s
BRmax
BRmax
R
Nominal value, ±10 %
Bmin
Permanent
R.m.s. value - important for cable dimensioning
current, r.m.s.
Switching
Minimum
threshold
brake resistor
(adjustable)
U
[V]
R
[Ω]
BRmax
Bmin
790
5.0
790
4.3
790
3.5
790
2.8
790
2.3
790
1.8
790
1.4
790
1.2
790
1.1
790
1.1
I
, P
Periodic load change of 0.5 s and recovery time of 4.5 s
BRmax
BRmax
R
Nominal value, ±10 %
Bmin
Permanent
R.m.s. value - important for cable dimensioning
current, r.m.s.
Technical data
Electrical data
Peak current
Peak braking
power
I
[A]
P
[kW]
BRmax
BRmax
145
105
169
122
207
150
259
188
315
229
414
300
518
375
604
438
659
478
659
478
Peak current
Peak braking
power
I
[A]
P
[kW]
BRmax
BRmax
158
125
184
145
226
178
282
223
343
271
451
357
564
446
658
520
718
567
718
567
3
Continuous
Continuous
current
braking
power
RMS
I
[A]
P
[kW]
BRd
Bd
79
31.5
93
36.7
113
45.1
142
56.3
173
68.6
227
90.1
227
90
287
99
300
99
300
99
Continuous
Continuous
current
braking
power
RMS
I
[A]
P
[kW]
BRd
Bd
87
37.4
101
43.5
124
53.5
154
66.9
188
81.4
247
107
289
117
312
117
327
117
327
117
77

Publicidad

Tabla de contenido
loading

Tabla de contenido