Rockwell Automation Allen-Bradley PowerFlex 40 Guia De Inicio Rapido página 10

Ocultar thumbs Ver también para Allen-Bradley PowerFlex 40:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 93
English-8
Control Terminal Block
Control Wiring Block Diagram
Enable
Jumper
Relay N.O.
R1
Relay Common
R2
Relay N.C.
R3
0-10V
0-20mA
R1 R2 R3
30V DC 125V AC 240V AC
Resistive
3.0A
3.0A
3.0A
Inductive
0.5A
0.5A
0.5A
P036 [Start Source]
Keypad
Per P037
3-Wire
Per P037
2-Wire
Per P037
RS485 Port
Per P037
Important: The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove
this jumper when using I/O Terminal 01 as a stop or enable input.
(2)
Two wire control shown. For three wire control use a momentary input
command a start. Use a maintained input
(3)
When using an opto output with an inductive load such as a relay, install a recovery diode parallel
to the relay as shown, to prevent damage to the output.
(4)
When the ENBL jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing
a coast to stop without software interpretation. Refer to the PowerFlex 40 User Manual for more
information.
(4)
SNK
SRC
30V DC
50mA
Non-inductive
Analog Output Select
01 02 03 04 05
SNK
11 12 13 14 15
SRC
(1)
Stop
I/O Terminal 01 Stop
Coast
Per P037
Coast
Coast
(1)(4)
Stop
01
Start/Run FWD
02
Direction/Run REV
03
Digital Common
04
Digital Input 1
05
Digital Input 2
06
Digital Input 3
07
Digital Input 4
08
Opto Common
09
+24V
+24V DC
11
+10V DC
+10V
12
0-10V (or ±10V) Input
13
Analog Common
14
4-20mA Input
15
0-10V
Analog Output
16
0/4-20mA
Opto Output 1
17
Opto Output 2
18
RS485 Shield
19
ENBL
06 07 08 09
16 17 18 19
(1)
Important: I/O Terminal 01 is always a coast to
stop input except when P036 [Start Source] is set to
"3-Wire" or "Momt FWD/REV" control. In three wire
control, I/O Terminal 01 is controlled by P037 [Stop
Mode]. All other stop sources are controlled by P037
[Stop Mode].
for I/O Terminal 03 to change direction.
Typical
Typical
SRC Wiring
SNK Wiring
(2)
Pot must be
1-10k ohm
2 Watt Min.
(3)
Common
24V
(4)
Enable
Jumper
RS485
(DSI)
1
on I/O Terminal 02 to

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Allen-bradley frn 5 serieAllen-bradley frn 6 serie

Tabla de contenido