Rockwell Automation Allen-Bradley PowerFlex 40 Guia De Inicio Rapido página 20

Ocultar thumbs Ver también para Allen-Bradley PowerFlex 40:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 93
English-18
No.
Parameter
A084 [Boost Select]
Only active when A125 [Torque Perf Mode] is
set to 0 "V/Hz".
A085 [Start Boost]
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to "0".
A086 [Break Voltage]
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to "0".
A087 [Break Frequency]
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to "0".
A088 [Maximum Voltage]
A089 [Current Limit 1]
A090 [Motor OL Select]
A091 [PWM Frequency]
A092 [Auto Rstrt Tries]
A093 [Auto Rstrt Delay]
A094 [Start At PowerUp]
A095 [Reverse Disable]
A096 [Flying Start En]
A097 [Compensation]
A098 [SW Current Trip]
A099 [Process Factor]
A100 [Fault Clear]
A101 [Program Lock]
A102 [Testpoint Sel]
A103 [Comm Data Rate]
Power to drive must be cycled before any
changes will affect drive operation.
A104 [Comm Node Addr]
Power to drive must be cycled before any
changes will affect drive operation.
A105 [Comm Loss Action] 0/3
A106 [Comm Loss Time]
A107 [Comm Format]
Power to drive must be cycled before any
changes will affect drive operation.
A108 [Language]
A109 [Anlg Out Setpt]
A110 [Anlg In 0-10V Lo]
A111 [Anlg In 0-10V Hi]
A112 [Anlg In4-20mA Lo]
A113 [Anlg In4-20mA Hi]
A114 [Slip Hertz @ FLA]
A115 [Process Time Lo]
See the PowerFlex 40 User Manual for more information on parameters.
Min/Max
Display/Options
0/14
Settings in % of base voltage.
0 = "Custom V/Hz"
Variable Torque
1 = "30.0, VT"
2 = "35.0, VT"
3 = "40.0, VT"
4 = "45.0, VT"
0.1%
0.0/25.0%
0.1%
0.0/100.0%
0.1 Hz
0.0/400.0 Hz
20/Rated Volts
1 VAC
0.1/(Drive Amps × 1.8) 0.1 Amps
0/2
0 = "No Derate"
2.0/16.0 kHz
0.1 kHz
0/9
1
0.0/300.0 Secs
0.1 Secs
0/1
0 = "Disabled"
0/1
0 = "Rev Enabled"
0/1
0 = "Disabled"
0/3
0 = "Disabled"
1 = "Electrical"
0.0/(Drive Amps × 2) 0.1 Amps
0.1/999.9
0.1
0/2
0 = "Ready/Idle"
0/9999
0 = "Unlocked"
400/FFFF
1 Hex
0/5
0 = "1200"
1 = "2400"
2 = "4800"
1/247
1
0 = "Fault"
1 = "Coast Stop"
0.1/60.0 Secs
0.1 Secs
0/5
0 = "RTU 8-N-1"
1 = "RTU 8-E-1"
2 = "RTU 8-O-1"
1/10
1 = "English"
2 = "Français"
3 = "Español"
4 = "Italiano"
5 = "Deutsch"
0.0/100.0%
0.1%
0.0/100.0%
0.1%
0.0/100.0%
0.1%
0.0/100.0%
0.1%
0.0/100.0%
0.1%
0.0/10.0 Hz
0.1 Hz
0.00/99.99
0.01
Constant Torque
5 = "0.0, no IR"
10 = "10.0, CT"
6 = "0.0"
11 = "12.5, CT"
7 = "2.5, CT"
12 = "15.0, CT"
8 = "5.0, CT"
13 = "17.5, CT"
9 = "7.5, CT"
14 = "20.0, CT"
1 = "Min Derate"
2 = "Max Derate"
1 = "Enabled"
1 = "Rev Disabled"
1 = "Enabled"
2 = "Mechanical"
3 = "Both"
1 = "Reset Fault"
2 = "Clear Buffer"
1 = "Locked"
3 = "9600"
4 = "19.2K"
5 = "38.4K"
2 = "Stop"
3 = "Continu Last"
3 = "RTU 8-N-2"
4 = "RTU 8-E-2"
5 = "RTU 8-O-2"
6 = "Reserved"
7 = "Português"
8 = "Reserved"
9 = "Reserved"
10 = "Nederlands"
Default
8
7 4-11 kW
(5-15 HP)
2.5%
25.0%
15.0 Hz
Rated Volts
Amps × 1.5
0
4.0 kHz
0
1.0 Secs
0
0
0
1
0.0 (Disabled)
30.0
0
0
400
3
100
0
5.0 Secs
0
1
0.0%
0.0%
100.0%
0.0%
100.0%
2.0 Hz
0.00

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Allen-bradley frn 5 serieAllen-bradley frn 6 serie

Tabla de contenido