baltur BT 320 Guía Rápida página 59

Sistema de control electronico
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Click up to increase the air opening position or down to decrease it.
Press ENTER to save the new settings.
Click up to quit the ignition position.
Check the combustion quality in all positions (from minimum to
maximum output) and adjust the gas and air setting if necessary
(as indicated on page 5).
Set the maximum load position 999, according to the maximum
output required by the boiler. If necessary, set the inlet gas pressure
(at the exit of the gas pressure reducer). check again the quality
combustion in all positions and adjust gas and air if necessary (see
page 5).
Press EXIT to quit the combustion settings.
7 / 50
0006081511_201311

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bt 330Bt 340

Tabla de contenido