Softwareversion; Serial Number - baltur BT 320 Guía Rápida

Sistema de control electronico
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

• The display shows the "Start-up counter" menu window.
Fig. 5-6 Display "Start-up counter"
1 pictogram burner start-up
2 Number of burner start-ups, oil operation
3 Number of burner start-ups, gas operation
5.4.2 r ecaLL FaULT HISTOrY
Display burner faults
• Use the cursor keys
confirm this with enter
The display shows the "Fault history selection" menu.
Fig. 5-7 Fault history selection menu
1
Burner fault pictogram [selected]
• Use the keys
to select the menu
firm with enter
.
The display shows the "Fault history" menu
Fig. 5-8 Fault history menu
1 error code-display pictogram
2 Fault code (the last 10 faults are stored, in which no. 01 is
the most recent fault)
3 Diagnostic code 1
4 Diagnostic code 2
5 Number of operating hours at the mo-ment, the fault occurs
i
Information concerning fault and diagnostic codes can be
found in the list of fault codes.To analyse a fault you always
need the fault code and the diagnostic code D1 or D2.
to select the menu
and
.
and con-
18 / 50
0006081511_201311

5.4.3 SOFTWareverSION

Display software version
• Use the cursor keys
confirm this with enter
The display shows the "Software version" menu.
Fig. 5-9 Software version menu
1 Software version pictogram
2 UI300 software version (user interface)
3 BT300 software version (BurnerTronic)
5.4.4 D ISpLaY OF cHeck SUMS
Display check sum
• Use the cursor keys
confirm this with enter
The display shows "CRC16 check sums" menu.
Fig. 5-10 CRC16 check sums menu
1 check sums pictogram
2 check sum, access level 0
3 check sum, access level 1
4 check sum, access level 2
5 check sum, access level 4
crc16 check sums
The check sums are formed from the device parameters. In each
case, the BT300 calculates a check sum for the parameters from
access levels 0, 1, 2 and 4. This is displayed as a hex-adecimal
value.The check sums are used to determine whether or not the
value for one or more parameters present in the corresponding
access level has been changed.
5.4.5 S erIaL NUMBer
Display serial number
• Use the cursor keys
to select the menu
and
.
to select the menu
and
.
to select the menu
and

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bt 330Bt 340

Tabla de contenido