Electrical installation

6.1

Important notes

Installation must
ƒ
always be in accordance with the operating conditions specified in the
Technical data ( 42).
be carried out to EN 60204-1.
Please observe the following when selecting the cable type:
ƒ
The cables used must comply with the approvals required for the
application (e. g. VDE, UL etc.).
Fuses and cable cross-sections must be dimensioned in accordance with
the specifications in the documentation for the basic device.
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
EDK94AZRP45 DE/EN/FR/ES/IT 5.0
Death or severe injuries when touching the power terminals.
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
Make sure that all power terminals are deenergised.
Death or severe injuries when the device is touched in the event
of a fault.
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor
diameter  10 mm
Electrical installation
Important notes
2
or PE conductor must be connected twice)
6
53